background image

CANopen encoder

14

Index S-Idx Name

Type,

access

default value

Description

100C 0

Guard time

u16, rw

0

This object contains the 'guard time' in

milliseconds�

100D 0

Life time factor

u8, rw

0

This object contains the life time factor

parameter� The life time factor multiplied

with the guard time results in the life time

for the guarding protocol�

1010

Store

parameters

This object is used to write the

parameters to the non-volatile memory�

0

Number of sub

indices

u8, ro

1

1

Store all

parameters

u32, rw

"save"

To write the parameters to the non-

volatile memory the word "save" has to

be sent to the corresponding node�

Most significant word

Least significant word

ASCII

e

v

a

s

Hex value

65h

76h

61h

73h

1011

Restore

parameters

The object is used to restore the factory

settings�

0

Number of sub

indices

u8, ro

1

1

Restore all

parameters

u32, rw

"load"

To restore the factory settings the

word "load" has to be sent to the

corresponding node� When the

parameters have been restored, please

check the parameters before the store

command is executed again� The

restored parameters only become active

after a reset or power up�

Most significant word

Least significant word

ASCII

d

a

o

l

Hex value

64h

61h

6Fh

6Ch