ifm electronic RM9000 User Manual

Page 20

Advertising
background image

CANopen encoder

20

Index S-Idx Name

Type,

access

default value Description

2102

0

Total

resolution

u32, rw

0x1000000

Total resolution of the encoder
This parameter is used to set the

requested total resolution� The parameter

must not exceed the physical measuring

range of the encoder� The total resolution

and the resolution per revolution must be

entered using the following formula:
GA = (PGA x AU) / PAU
PGA

total physical resolution of the encoder

(see type label)
PAU

physical resolution per revolution of the

enocder (see type label)
GA

total resolution (customer-specific)
AU

resolution per revolution (customer-

specific)
If the requested total resolution is lower

than the total physical resolution, the total

resolution parameter must be a multiple of

the physical resolution per revolution�

2103

0

Preset value

u32, rw

0

The preset value is a position value which

is to be indicated at a certain physical

position of the axis� The preset value must

not exceed the total physical resolution to

avoid runtime errors�

2104

0

Limit switch,

min�

u32, rw

0

Two position vaues can be programmed as

limit switch positions� When one of these

values has been reached, one of the 32-bit

position values is set� Both values must not

exceed the total physical resolution of the

encoder to avoid runtime errors�

The limit switch (min) sets bit 30 = 1 with the next telegram transmitted when the set position value

has been reached or fallen below�

Function Status bit Process value
Bit

31

30

29

28

27

26

25�����0

0

1

X

X

X

X

X