N” series - installation and connection, Plumbing, Electrical – Insinger I Series Food Waste Disposer User Manual

Page 6: Testing

Advertising
background image

Page 6

Insinger Machine Company 2005

“N” SERIES - Installation and Connection

NOTE: PLUMBING AND ELECTRICAL CONNECTIONS SHALL BE MADE IN COMPLIANCE WITH APPLICABLE
LOCAL CONSTRUCTION CODES.

PLUMBING

Inlet: Cold water supply to disposer shall be 1/2" service line with a minimum of 20 lbs. flow pressure, piped as close
to disposer as possible. All disposer and control connections shall be 1/2" pipe size.

Sewer Outlet: 2" waste line should have trap with conveniently located clean out. Do not connect through a grease trap.
Avoid bends, elbows, tees, etc., to reduce the possibility of plumbing stoppage. A globe valve, used for metering flow,
must be installed between solenoid valve and cone or sink. Water swirl inlet valves should be located nearest operator.

See Typical Installation Diagram.

ELECTRICAL

Follow guidelines set forth by NEC standards. Disposer branch circuit shall be sized and fused (circuit breakers) as
required by motor. The disposer must be connected to a grounded, metal, permanent wiring system; or a disposer-
grounding conductor must be run with the circuit conductors and connected to the disposer-grounding terminal or lead
on disposer. All connections, junction boxes and conduits must be watertight (NEMA 4).

TESTING

See Start-up and Run Section.

SINGLE PHASE

THREE PHASE

115 Volt, 60 Hz

230 Volts, 60 Hz

208/230 Volt, 60 Hz

460 Volt, 60 Hz

110 Volt, 50 Hz

220 Volts, 50 Hz

190-220 Volts, 50 Hz 380-440 Volts, 50 Hz

Tied Together and Insulated
Insulated

**

**

T1

T4
P4
T2
T8
T5
P5
T3
T9
T6
P6

T7

L1

L2

L3

L1

L2

L3

**

T1

T4
P4
T2
T8
T5
P5
T3
T9
T6
P6

T7

*

**

P1

T8
P2
T3

T5
T2
T4

L2

L1

MOTOR WIRING DIAGRAM

VOLTAGE-AMPERAGE TABLE

INSTALLATION DIAGRAM

1” Min.
6” Max.

1” Min.
6” Max.

1” Min.
6” Max.

1” Min.
6” Max.

Disposer shown with regular 7” drum

and sink mounting assembly

Note: All dimensions shown at 0” foot height adjustment

8” length of neoprene connector
sleeve furnished. May be cut to
desired length.

Adjustable 0” to 2”

Disposer shown with offset drum and

cone mounting assembly

4 1/2” regular drum with
sink mounting assembly

Table Cutout

13” for 12” cone
16” for 15” cone
19” for 18” cone

1”

5” for 12” cone
6” for 15” cone
7” for 18” cone

1”

1”

1”

4 1/2”

6 1/4”

8”

14 1/2”

27”

8”

7”

5” for 12” cone
6” for 15” cone
7” for 18” cone

6 1/4”

8”

Adjustable 0” to 2”

19”

23”

14 1/2”

7”

8”

Water

inlet

Drain

4 1/2” regular drum with

cone mounting assembly

Drain

Cutout 5 1/2”

4 1/2” inside
diameter

HP

SINGLE PHASE

THREE PHASE

Volts

Amps*

Volts

Amps*

1 1/2

115

230

17.2

8.6

208
230
460

4.9
4.4
2.2

2

115

230

18.4

9.2

208
230
460

6.9
6.2
3.1

3

NA

208
230
460

9.7
8.8
4.4

*Ratings are for 60 Hz operation.