Measurement Computing DAQFlex User Guide User Manual

Page 100

Advertising
background image

DAQFlex Software User's Guide

Hardware Reference – USB-200 Series

100

Component

Supported
Property/Command

Set/Get

Supported Values

SAMPLES

Set/Get

0 to N

(0 = continuous scan; N = 32-bit FIFO)

SCALE

Set/Get

ENABLE, DISABLE

START

Set

STATUS

Get

IDLE, RUNNING, OVERRUN

STOP

Set

TRIG

Set/Get

ENABLE, DISABLE

XFRMODE

Set/Get

BLOCKIO, SINGLEIO

AITRIG

SRC

Set/Get

HWSTART/DIG

Type

Set/Get

EDGE/RISING, EDGE/FALLING
LEVEL/HIGH, LEVEL/LOW

AO

1

Get

2

RES

Get

U12 (unsigned 12-bit integer)

SCALE

Set/Get

ENABLE, DISABLE

AO{ch}

1

RANGE

Get

UNI5V

VALUE

Set

0 to 4,095
0 to 4.99838 when SCALE is enabled

CTR

Get

1

CTR{ch}

START

Set

STOP

Set

VALUE

Get

0 to 4,294,967,295

Set

0 (resets the counter to 0)

DEV

FLASHLED/{n}

Set

0 to 255

FWV

Get

MM.mm (M = major; m = minor)

ID

Set/Get

Up to 56 characters

MFGCAL

Get

yyyy-mm-dd HH:MM:SS

MFGCAL{item}

Get

YEAR as yyyy; 20xx
MONTH as mm; 01 to 12

DAY as dd; 01 to 31

HOUR as HH; 01 to 23

MINUTE as MM; 01 to 59

SECOND as SS; 01 to 59

MFGSER

Get

Up to 8 hexadecimal digits

RESET/{value}

Set

DEFAULT

DIO

Get

1

DIO{port}

Get

8

DIR

Set/Get

IN, OUT

LATCH

Set/Get

0 to 255

VALUE

Set/Get

0 to 255

Advertising