Montigo E36DV-TV User Manual

Page 5

Advertising
background image

0 9 / 9 6

Page 5 of 14

E36DV-TV

2 Feet

Support ring
Support plate

Storm collar

Roof flashing

Firestop

Minimum 1"
clearance to all
combustibles
materials

FIGURE 9A.

Support ring

Support straps

Firestop

Support ring
Support plate

Firestop

20 Feet

2'

FIGURE 9B.

2 Feet

Minimum 1"

clearance to all

combustibles

materials

A complete Econo Plus 36DV-TV vertical vent installation may
comprise of the following components:

A - Termination

MVTK-1

B - Flex sections

MFL-1 (1' 6" section)
MFL-2 (2' 6" section)
MFL-3 (3' 6" section)
MFL-4 (4' 6" section)

C - Solid sections

MEXT-1 (1' section)
MEXT-2 (2' section)
MEXT-3 (3' section)
MEXT-4 (4' section)
MEXT-6 (6' Section)

D - Support Ring & Plate

MSPXT-7 (7" Support
Plate & Ring)

E - 7" Firestop

FS-7 (7" Firestop)

F - Roof Flashing

MRF-16 (1/12 to 6/12 pitch)
MRF-12 (6/12 to 12/12 pitch)

VERTICAL DIRECT VENT TERMINALS

Shall not be installed;

- Less than two feet above the highest point where vent

passes through the roof.

- Less than six feet from a mechanical air inlet.

- Less than three feet from a parapet wall.

Offsets;

- A maximum of two offsets with 90 degree bends may

be made and shall not exceed total length of 25% of
the vertical vent height, when measured center to
center of piping.

EXAMPLE:

Typical vent installaion

(see figure 2)

20' vertical vent
2 - 2' offsets required
25% of 20' = 4' max. offset allowed
this venting system complies to
instruction requirements.

- Maximum vent height is 28 feet above fireplace.

- Minimum clearances 1" from vent to all combustible

materials must be maintained.

INSTALLATION OF VERTICAL DIRECT VENT