Installation, Top vent venting runs, Installation of top vent dv – Montigo M38ODV ST User Manual

Page 6

Advertising
background image

XG0128

Page 6

M38ODV-ST Direct Vented Fireplace

Installation

Top Vent Venting Runs

Before you install any venting, you must determine whether the venting
run will be acceptable. Unacceptable venting can affect the fireplace's
combustion.

„

for installations with horizontal venting runs of 0-16 feet, use the
vent graph, as described below

„

the maximum horizontal vent run is 16 feet.

The Venting Graph

Measure the vertical height from the fireplace hearth to the centre of
the termination and the horizontal run from the from the fireplace flue
collar to the wall flange of the termination. Plot on the Venting Graph
(Fig. 4) with an 'X'.

If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.

Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 72", and the horizontal
run to the wall flange of the vent termination is 120", this would be
an acceptable installation.

Example B: (Acceptable Installation)

If the vertical dimension from the hearth is 66" and the horizontal
run to the wall flange of the vent termination is 30", this would be
an acceptable installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 48" and
the horizontal run to the wall flange of the vent termination is 84",
this would NOT be an acceptable installation.

Installation Of Top Vent DV

A complete M38ODV-ST vent system may comprise up to six different
types of components:

A - Termination

PTO-3 (3" length)

PTO-3F (3" length)

B - Stucco Kits

MSR (stucco frame)

MOSR (stucco can)

C - Flex sections

PFL-1 (12" section)

PFL-2 (24" section)

PFL-3 (36" section)

PFL-4 (48" section)

D - Solid sections

PEXT-1 (12" section)

PEXT-2 (24" section)

PEXT-3 (36" section)

PEXT-4 (48" section)

E - 90° elbow

PEL-90

90° elbow

PEL-90

90° elbow

PEL-90

F - Offset Box

DVST-CNT

Figure 4.

Venting Graph.

Height to center

of vent pipe.

Hearth

1

1

2

3

4

5

6

7

8

2

3

4

5

6

7

8

9 10 11 12 13 14 15 16

Vent may not terminate

in shaded area.

Vent

terminate

in this area.

may

Vent Rise (feet)

Vent Run (feet)