System-10 btu meter bacnet driver – ONICON System-10 Dualnet User Manual

Page 16

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10 Dual Network Interface Installation Guide 05/14 - 0972-1

Page

16

SECTION 2.0: BACnet PICS AND OBJECTS

2.1 PIC STATEMENTS

SYSTEM-10 BTU METER BACNET DRIVER

Protocol Implementation Conformance Statement (PICS)

BACnet Protocol

Date:

August 16, 2005

Vendor Nam

e:

ONICON Incorporated

Product Nam

e:

Sy

stem

-10 Btu Meter

P

ro

d

u

ct

M

o

d

el

:

S

Y

S

T

E

M

-1

0

-B

A

C

Product Description:

The Sy

stem

-10 BTU Meter provides highly

accurate therm

al energy

m

easurem

ent in chilled water,

hot water and condenser water

sy

stem

s based on signal inputs from

two m

atched tem

perature sensors

(included) and any

of ONICON's insertion or inline flow m

et

ers (ordered separately

). The

Sy

stem

-10-BAC provides energy

, flow and tem

perature data on a lo

cal alphanum

eric display

and to the network via the BACnet com

m

unications MS/TP driver.

An optional auxiliary

input is also available to totalize pul

ses from

another device and com

m

unicate the total directly

to the

network.

BACnet Standardiz

ed Device Profile (Annex L):

BACnet Sm

art Sensor (B-SS)

BACnet Sm

art Actuator (B-SA)

BACnet Application Specific Controller (B-ASC)

BACnet Interoperability Building Blocks Supported (Annex K):

K.1.2 BIBB – Data Sharing – ReadProperty

-B (DS-RP-B)

K.1.8 BIBB – Data Sharing – WriteProperty

-B (DS-WP-B)

K.5.2 BIBB – Device Managem

ent – Dy

nam

ic Device

Binding-B (DM-DDB-B)

Segmentation Capability:

None

Standard Object Types Supported:

Device Object

Multi State Input Output

Analog Input

Multi St

at

e Output

Analog Output

Multi State Value

Analog Value

Binary

Input

Binary

Output

Binary

Value

For all these properties the following apply:

1.

Does not support BACnet CreateObject

2.

Does not support BACnet DeleteObject

3.

Does not support any

optional properties

4.

No additional writeable properties exist

5.

No proprietary

properties exist

6.

No range restrictions exist

Data Link Layer Options:

MS/TP

m

aster (Clause 9), baud rate up to

76800 bps

MS/TP slave (Clause 9), baud rate up to

76800 bps

Device Address Binding:

Not supported

Character Sets Supported:

ANSI X3.4.

1500 North Belcher Road, Clearwater

, FLorida 33765 • (727) 447-6140 • (727) 442-5699

www

.onicon.com • [email protected]

03-19-08

x

x

x