ONICON System-10 Dualnet User Manual

Page 22

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10 Dual Network Interface Installation Guide 05/14 - 0972-1

Page

22

REGISTER

ADDRESS

DESCRIPTION

REGISTER TYPE

READ/

WRITE

COMMENT

41035

Energy Total Mode 1 –Btu

Floating point register (1 of 2)

Read Only

41036

Energy Total Mode 1 –Btu

Floating point register (2 of 2)

Read Only

41037

Energy Total Mode 2 –Btu

Floating point register (1 of 2)

Read Only

41038

Energy Total Mode 2 –Btu

Floating point register (2 of 2)

Read Only

41039

Energy Total Mode 1 – TonHr

Floating point register (1 of 2)

Read Only

41040

Energy Total Mode 1 – TonHr

Floating point register (2 of 2)

Read Only

41041

Energy Total Mode 2 – TonHr

Floating point register (1 of 2)

Read Only

41042

Energy Total Mode 2 – TonHr

Floating point register (2 of 2)

Read Only

41043

Energy Total Mode 1 – kWHr

Floating point register (1 of 2)

Read Only

41044

Energy Total Mode 1 – kWHr

Floating point register (2 of 2)

Read Only

41045

Energy Total Mode 2 – kWHr

Floating point register (1 of 2)

Read Only

41046

Energy Total Mode 2 – kWHr

Floating point register (2 of 2)

Read Only

41047

Volume Total Mode 1 –Gal

Floating point register (1 of 2)

Read Only

41048

Volume Total Mode 1 –Gal

Floating point register (2 of 2)

Read Only

41049

Volume Total Mode 2 –Gal

Floating point register (1 of 2)

Read Only

41050

Volume Total Mode 2 –Gal

Floating point register (2 of 2)

Read Only

41051

Volume Total Mode 1 – Liters

Floating point register (1 of 2)

Read Only

41052

Volume Total Mode 1 – Liters

Floating point register (2 of 2)

Read Only

41053

Volume Total Mode 2 – Liters

Floating point register (1 of 2)

Read Only

41054

Volume Total Mode 2 – Liters

Floating point register (2 of 2)

Read Only

41055

Volume Total Mode 1 – M³

Floating point register (1 of 2)

Read Only

41056

Volume Total Mode 1 – M³

Floating point register (2 of 2)

Read Only

41057

Volume Total Mode 2 – M³

Floating point register (1 of 2)

Read Only

41058

Volume Total Mode 2 – M³

Floating point register (2 of 2)

Read Only

41079

Volume Total Mode 1 – Ft³

Floating point register (1 of 2)

Read Only

41080

Volume Total Mode 1 – Ft³

Floating point register (2 of 2)

Read Only

41081

Volume Total Mode 2 – Ft³

Floating point register (1 of 2)

Read Only

41082

Volume Total Mode 2 – Ft³

Floating point register (2 of 2)

Read Only

41059

Mass Total –Lbs

Floating point register (1 of 2)

Read Only

Mass units are only

available when using

F-2000 Vortex meter

41060

Mass Total –Lbs

Floating point register (2 of 2)

Read Only

41061

Mass Total –kg

Floating point register (1 of 2)

Read Only

41062

Mass Total –kg

Floating point register (2 of 2)

Read Only

41063

Auxiliary Input Total (Di3)

Floating point register (1 of 2)

Read Only

41064

Auxiliary Input Total

Floating point register (2 of 2)

Read Only

REGISTER

ADDRESS

DESCRIPTION

REGISTER

TYPE

DATA

RANGE

OVER

RANGE

READ/

WRITE

COMMENT

41065

Zero Mode 1 Energy Total

0 – 1

0 – 1

N/A

Read/Write

Write a value of 1 to

registers to reset totals.

Re-write a value of zero

to the register once the

totals reset.

41066

Zero Mode 1 Volume Total

0 – 1

0 – 1

N/A

Read/Write

41067

Zero Mode 2 Energy Total

0 – 1

0 – 1

N/A

Read/Write

41068

Zero Mode 2 Volume Total

0 – 1

0 – 1

N/A

Read/Write

41069

Zero Auxiliary Input Total (Di3)

0 – 1

0 – 1

N/A

Read/Write

Advertising