ONICON System-10 Dualnet User Manual

Page 25

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10 Dual Network Interface Installation Guide 05/14 - 0972-1

Page

25

3.3 TOTALIZATION, RESETTING TOTALS, OVER-RANGE & ROLLOVER

A. Integer Register Totalization

Holding registers 40026 through 40061 are integer registers that provide totalized energy,

volume and mass flow data in a variety of engineering units. The registers are organized into

pairs or groups of three.

The first (low order) register is limited to a range of 0 – 999. This register rolls over to zero when

the total value reaches 1,000. If the registers are in a group of three, the second register (middle

order) is also limited to a range of 0 – 999. This register also rolls over when the register value

reaches 1,000.

The second, or in the case of groups of three, third, (high order) register is scaled such that

the smallest incremental value indicated is 1,000 times greater than the preceding register. An

example of this is shown below.

Example - A group of 3 registers

Register

Engineering units & Scaling

Current Value

40026

kBtu (Btu x 1,000)

00500

40027

MBtu (Btu x 1,000,000)

00015

40028

GBtu (Btu x 1,000,000,000)

00111

Low order + middle order + high order = Btu Total = 111,015,500,000

or

kBtu Total = 111,015,500

Registers 40062 and 40063 provide totalization for the optional auxiliary pulse input option of

the System-10 BTU Meter. There are no engineering units associated with these registers.

B. Floating Point Totalization

Registers 41003 through 41064 provide energy, volume and mass flow data in 32 bit single

precision floating point format. The registers are organized into pairs. Each pair must be

concatenated according to IEEE 754.

Register order: Most significant first, least significant second.

Word order: Most significant value first, least significant value second.

Byte order within each word: Most significant byte first.

Bit order within each byte: Most significant bit first.

Registers 41063 and 41064 provide totalization for the optional auxiliary pulse input option of

the System-10 BTU Meter. There are no engineering units associated with these registers.

Advertising