ONICON System-10 Dualnet User Manual

Page 6

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10 Dual Network Interface Installation Guide 05/14 - 0972-1

Page

6

1.4 PROTOCOL SELECTION

The System-10 Dual Network BTU Meter is provided with an IP connection and a single RS485

connection. Both MODBUS TCP/IP and BACnet UDP/IP are always available from the IP

connection via a single IPv4 IP address. The RS485 connection can be configured for BACnet

MS/TP or MODBUS RTU. The protocol options are selected via dip switch settings. The table

below identifies the dip switch settings for each protocol. The switch settings also control

which network is allowed to remotely reset totals on the network.

Dip switch SW3 Protocol selection and reset function settings

Protocols

Reset

1

2

3

4

BACnet IP/Modbus TCP/Modbus RTU

None

Off

Off

Off

Off

BACnet IP/Modbus TCP/Modbus RTU

BACnet IP

On

Off

Off

Off

BACnet IP/Modbus TCP/Modbus RTU

Modbus TCP

Off

On

Off

Off

BACnet IP/Modbus TCP/Modbus RTU

Modbus RTU

On

On

Off

Off

BACnet IP/Modbus TCP/BACnet MSTP

None

Off

Off

On

Off

BACnet IP/Modbus TCP/BACnet MSTP

BACnet IP

On

Off

On

Off

BACnet IP/Modbus TCP/BACnet MSTP

Modbus TCP

Off

On

On

Off

BACnet IP/Modbus TCP/BACnet MSTP

BACnet MS/TP

On

On

On

Off

Baud Rate Dip

Switches

(See Section 1.6.1)

Protocol Selection

Switches