Reported Problem

Possible Solutions

Network communications are
disrupted when the device is
connected.

• The RS485 network cable connections are polarity

sensitive and must be connected the same way on
every device (i.e. + to + and - to -). (See section 1.4.1 of
this manual for details.)

• Is the transmit LED flashing? The transmit LED will

only flash when the device is responding to a poll.
A unique address is required for each device on the
network. Duplicate addresses will cause some or all
of the devices on the network to quit working. (See
section 1.6.1 of this manual for details.)

• A unique IP address is required for each device on

TCP/IP networks. Duplicate addresses will cause
multiple devices to respond to the same poll. This will
cause some or all of the devices on the network to quit
working. (See section 1.6.2 of this manual for details.)

Network communications are
disrupted when the device is
connected (cont.).

• Shield drain connections should be daisy

chained in the same manner as the

signal cables for RS485. The shield drain

wire should be left unterminated at the

end of the cable and connected to earth

only at the network master controller.

Shield wires must not be connected to the

RS485 connector on the D-100.