D-100 Display Module BACnet Installation and Operation Guide 05/14 - 0635-6 / 18341

Page 5

D-100

SCROLL RESET PROGRAM

ONICON

3864

Steam

Building

Domestic Water Supply

Flow rate and total data to

Data Acquisition System or

Building Control System

120VAC or 24VAC

Input Voltage

1.3 SPECIFICATIONS

BACnet NETWORK INTERFACE

MS/TP RS485

Transceiver: 2-wire, half-duplex

MAC address (device address) range: 1 - 254 (Default: 017)

Device Instance: 0-4,194,303 (Default: 57017)

Baud rate: 9600, 19200, 38400, 76800 or Auto-Baud (Default: Auto)

Termination: 120 ohms or none (Default: none)

Biasing: None

Flow control: None

UDP/IP

Transceiver: Base 10T, 10Mbps, Rj45 connection

Device Instance: 0 - 4,194,303 (Default: 57017)

Default IP address: 192.168.1.24 (Subnet Mask 255.255.255.0) (Port 47808)

Flow control: None

SECTION 1: INTRODUCTION

1.1 PURPOSE OF THIS GUIDE

The purpose of this guide is to provide installation and commissioning procedures and basic

operating and servicing instructions for the ONICON D-100 BACnet serial interface.

1.2 TYPICAL D-100 FLOW DISPLAY

The D-100 is a totalizing display module that provides a local indication of liquid, gas or

steam flow rate and total data. It can also be provided with an optional BACnet MS/TP or

BACnet/IP serial interface to communicate data to the building control network.