Stratford

Fireplace Installation and Operation Manual

_____________________________________________________________________ 41

Thermal Characteristics of Common Floor Protection Materials*

MATERIAL

CONDUCTIVITY (k)

PER INCH

RESISTANCE (R) PER INCH

THICKNESS

Micore

®

160

0.39

2.54

Micore

®

300

0.49

2.06

Durock

®

1.92

0.52

Hardibacker

®

1.95

0.51

Hardibacker

®

500

2.3

0.44

Wonderboard

®

3.23

0.31

Cement mortar

5.00

0.2

Common brick

5.00

0.2

Face brick

9.00

0.11

Marble

14.3 – 20.00

0.07 – 0.05

Ceramic tile

12.5

0.008

Concrete

1.050

0.950

Mineral wool insulation

0.320

3.120

Limestone

6.5

0.153

Ceramic board (Fibremax)

0.450

2.2

Horizontal still air** (1/8")

0.135

0,920**

* Information as reported by manufacturers and other resources

** For a 1/8" thickness. You cannot «stack» horizontal still air to accumulate R-values; you must
separate each layer of horizontal still air with another non-combustible material.

6.3.2

MINIMUM HEART EXTENSION REQUIREMENTS

The hearth extension floor area must extend at least 16" (41 cm) in front of the hearth (A) and at
least 8" (20 cm) on each side of the door opening (D). The joint between the hearth extension and
the fireplace hearth needs to be made of non-combustible material such as sheet metal (not
included).