The following information should be used for determining the proper location of the vent
terminal for direct vent tankless water heaters.

V VENT TERMINAL

X AIR SUPPLY INLET

AREA WHERE TERMINAL IS NOT PERMITTED

Horizontal Vent Terminal Location

1

In accordance with current CSA-B149.1 Installation Codes.

2

In accordance with current ANSI Z223.1/ NFPA 54 National Fuel Gas Code.

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family

dwellings and serves both dwellings.

*

For clearances not specified in ANSI 223.1/NFPA 54 or CSA-B149.12, one of the following shall be indicated:

a)

A minmum clearance value determined by testing in accordance with section 2.20, or;

b)

A reference to the following footnote: "Clearance in accordance with local installtion codes and the require-

ments of the gas supplier."

H = Clearance to each side of center line

extended meter/regulator assembly.
above

3 feet (91 cm) within a height 15 feet

(4.57 m) above the meter/regulator

assembly.

*

I = Clearance to service regulator

concentric vent outlet.

3 feet (91 cm)

*

J = Clearance to nonmechanical air

supply inlet to

the combustion

air inlet to any

building or other

appliance.

6 inches (15 cm) for appliances <

10,000 Btuh (3 kW), 12 inches (30 cm)

for appliances > 10,000 Btuh (3kW)

and < 100,000 Btuh (30kW), 36 inches

(91 cm) for appliances > 100,000 Btuh

(30kW).

6 inches (15 cm) for appliances < 10,000

Btuh (3 kW), 9 inches (23 cm) for

appliances > 10,000 Btuh (3kW) and <

50,000 Btuh (15kW), 12 inches (30 cm)

for appliances > 50,000 Btuh (15kW).

K = Clearance to mechanical

air supply

inlet.

6 feet (1.83 m)

3 feet (91 cm) above if within 10 feet

(3 m)

horizontally.

L = Clearance above paved sidewalk or

paved driveway

located

on public

property.

7 feet (2.13 m)†

*

M = Clearance under veranda, porch,

deck or balcony.

Not Allowed

Not Allowed

Canadian Installations

1

US Installations

2

A= Clearance above grade, veranda,

porch, deck or balcony.

12 inches (30 cm) above anticipated

snow level.

12 inches (30 cm) above anticipated

snow level.

B= Clearance to window or door that

may be opened.

6 inches (15 cm) for appliances < 10,000

Btuh (3 kW), 12 inches (30 cm) for

appliances > 10,000 Btuh (3kW) and <

100,000 Btuh (30kW), 36 inches (91 cm)

for appliances > 100,000 Btuh (30kW).

6 inches (15 cm) for appliances <

10,000 Btuh (3 kW), 9 inches (23 cm)

for appliances > 10,000 Btuh (3kW)

and < 50,000 Btuh (15kW), 12 inches

(30 cm) for appliances > 50,000 Btuh

(15kW).

C= Clearance to permanently closed

window.

*

*

D= Vertical Clearance to ventilated

soffit located above the terminal
within a horizontal distance of 2
feet (61 cm) from the center line of
the terminal.

*

*

E= Clearance to unventilated soffit.

*

*

F= Clearance to outside corner.

*

*

G= Clearance to corner.

*

*

11