Super Systems 7EK 31080 Calibration Manual User Manual

Page 4

Advertising
background image

4

The "PH" calibration is correct if the indication is equal to "P. 3

0000" + 10 counts.

1) Check the zero calibration, by making the short circuit as

described at point C.1, the read-out must be equal to "P. 0 0000"

+ 10 counts.

2) Remove the short circuit.

3) Connect the calibrator as shown in Fig. 7.

4) Check the linearity by setting the calibrator to 125.00 Ω. The

read-out must be "P. 1 0190" + 10 counts.

5) Set the calibrator to 250.00 Ω. The read-out must be "P. 2

0189" + 10 counts.

6) Push FUNC pushbutton, the instrument will go to the next

calibration group.

D) mA INPUT CALIBRATION

D.1) "nAL" - INITIAL SCALE VALUE

The lower display will show "nAL" while the upper display will show

"OFF"

1) Make the specific hardware setting as described at paragraph 2.

2) Connect the instrument under test to the calibrator as shown in

Fig. 6.

Fig. 6

3) Set calibrator to 0.000 mA.

4) Push ▲or ▼ pushbutton, the upper display will change to "On".

5) After a few seconds, start the calibration by pushing FUNC

pushbutton. At the end of this calibration routine, the instrument

will go to the next step.

D.2) "nAH" - FINAL SCALE VALUE

The lower display will show "nAH" while the upper display will show

"OFF"

1) Set the calibrator to 20.000 mA.

2) Push ▲ or ▼ pushbutton, the upper display will change to "On".

3) After a few seconds, start the calibration by pushing FUNC

pushbutton. At the end of this calibration routine, the instrument

will go to the next step.

D.3) "nA." - mA INPUT CHECK

The upper and lower show "nA." followed by the measured value in

counts.

The "nAH" calibration is correct if the indication is equal to "nA.

3 0000" + 10 counts.

1) Check the zero calibration, by setting the calibrator to 0.000 mA,

the read-out must be equal to "nA. 0 0000" + 10 counts.

2) Check the linearity by setting the calibrator to 10.000 mA , the

read-out must be "nA. 1 5000" + 10 counts.

NOTE: when it is desired to use a different check point, the

following formula describes the ratio between the signal input

and the instrument read-out (in counts).

Instrument readout (in counts) = input value

20 (mA)

30000

3) Push FUNC pushbutton, the instrument will go to the next

calibration group.

E) 5 V INPUT CALIBRATION

E.1) "5UL" - INITIAL SCALE VALUE

The lower display will show "5UL" while the upper display will show

"OFF"

1) Make the specific hardware setting as described at paragraph 2.

2) Connect the instrument under test to the calibrator as shown in

Fig. 7.

Fig.7

3) Set calibrator to 0.000 V.

4) Push ▲ or ▼ pushbutton, the upper display will change to "On".

5) After a few seconds, start the calibration by pushing FUNC

pushbutton. At the end of this calibration routine, the instrument

will go to the next step.

E.2) "5UH" - FINAL SCALE VALUE

The lower display will show "5UH" while the upper display will show

"OFF"

1) Set the calibrator to 5.000 V.

2) Push ▲ or ▼ pushbutton, the upper display will change to "On".

3) After a few seconds, start the calibration by pushing FUNC

pushbutton. At the end of this calibration routine, the instrument

will go to the next step.

E.3) "5U." - 5 V INPUT CHECK

The upper and the lower displays show "5U." followed by the

measured value in counts.

The "5UH" calibration is correct if the indication is equal to "5U. 3

0000" + 10 counts.

1) Check the zero calibration, by setting the calibrator to 0.0000 V,

the read-out must be equal to "5U. 0 0000" + 10 counts.

2) Check the linearity by setting the calibrator to 2.500 V The read-

out must be "5U. 1 5000" + 10 counts.

NOTE: when it is desired to use a different check point, the

following formula describes the ratio between the signal input

and the instrument read-out (in counts).

Instrument readout (in counts) = input value

5 (V)

30000

3) Push FUNC pushbutton, the instrument will go to the next

calibration group.

F) 10 V INPUT CALIBRATION

F.1) "10UL" - INITIAL SCALE VALUE

The lower display will show "10UL" while the upper display will

show "OFF"

1) Make the specific hardware setting as described at paragraph 2.

2) Connect the instrument under test to the calibrator as shown in

Fig. 8.

Fig.8

1

_

+

3

1

_

+

3

1

_

+

3

Check symbol

Measured or generated

value (in counts)

Check symbol

Measured or generated

value (in counts)