Super Systems 7EK 31080 Calibration Manual User Manual

Page 5

Advertising
background image

5

3) Set calibrator to 0.000 V.

4) Push ▲ or ▼ pushbutton, the upper display will change to "On".

5) After a few seconds, start the calibration by pushing FUNC

pushbutton. At the end of this calibration routine, the instrument

will go to the next step.

F.2) "10UH" - FINAL SCALE VALUE

The lower display will show "10UH" while the upper display will

show "OFF"

1) Set the calibrator to 10.000 V.

2) Push ▲ or ▼ pushbutton, the upper display will change to "On".

3) After a few seconds, start the calibration by pushing FUNC

pushbutton. At the end of this calibration routine, the instrument

will go to the next step.

F.3) "10U." - 10 V INPUT CHECK

The upper and the lower displays show "10U." followed by the

measured value in counts.

The "10U." calibration is correct if the indication is equal to "10U.3

0000" + 10 counts.

1) Check the zero calibration, by setting the calibrator to 0.000 V,

the read-out must be equal to "10U.0 0000" + 10 counts.

2) Check the linearity by setting the calibrator to 5.000 V The read-

out must be "10U.1 5000" + 10 counts.

NOTE: when it is desired to use a different check point, the

following formula describes the ratio between the signal input

and the instrument read-out (in counts).

Instrument readout (in counts) = input value

10 (V)

30000

3) Push FUNC pushbutton, the instrument will go to the next

calibration group.

G) CURRENT TRANSFORMER INPUT CALIBRATION

G.1) "ct.L" - INITIAL SCALE VALUE

The lower display will show "ct.L" while the upper display will show

"OFF"

1) Made the specific hardware setting as described at paragraph 2.

2) Connect the instrument under test to the calibrator as shown in

Fig. 9.

Fig.9

3) Set calibrator to 0.00 mA AC.

4) Push ▲ or ▼ pushbutton, the upper display will change to "On".

5) After a few seconds, start the calibration by pushing FUNC

pushbutton. At the end of this calibration routine, the instrument

will go to the next step.

G.2) "ct.H" - FINAL SCALE VALUE

The lower display will show "ct.H" while the upper display will show

"OFF"

1) Set the calibrator to 50.00 mA AC.

2) Push ▲ or ▼ pushbutton, the upper display will change to "On".

3) After a few seconds, start the calibration by pushing FUNC

pushbutton. At the end of this calibration routine, the instrument

will go to the next step.

Check symbol

Measured or generated

value (in counts)

6

5

mA AC

Generator

Check symbol

Measured or generated

value (in counts)

G.3) "ct." - CURRENT TRANSFORMER INPUT CHECK

The upper and the lower displays show "Ct." followed by the

measured value in counts.

The "ct.H" calibration is correct if the indication is equal to "ct. 0

1000" + 10 counts.

1) Check the zero calibration, by setting the calibrator to 0.00 mA

AC, the read-out must be equal to "ct. 0 0000" + 10 counts.

2) Check the linearity by setting the calibrator to 25.00 mA AC. The

read-out must be "ct. 0 0500" + 10 counts.

NOTE: when it is desired to use a different check point, the

following formula describes the ratio between the signal input

and the instrument read-out (in counts).

Instrument readout (in counts) = input value

50 (mA AC)

1000

3) Push FUNC pushbutton, the instrument will go to the next

calibration group.

H) DEFAULT CALIBRATION PARAMETER LOADING.

A complete and consistent set of calibration parameters is memorized

in the instrument. These data are theoretical data and are used only

to clear all calibration memory but after a default calibration data

loading it is necessary to make

all calibrations.

When is desired to clear all calibration memory proceed as follows:

a) The upper display will show "CAL" while the lower display is blank.

b) Push the▼ push-button, the lower display will show the firmware

version.

c) Push and keep depressed the ▼ push-button again and push the

push-button, the lower display will show "dFLt".

d) Push ▲ or ▼ pushbutton, the upper display will change to "On".

e) Push the FUNC push-button, the upper display will show:

Then the upper display will show CAL again and the default calibra-

tion parameter loading procedure is ended.

WARNING: After default calibration data loading, it is

necessary to remake

all instrument calibrations.