Outputs tab – Wavetronix SmartSensor HD (101-0415) - User Guide User Manual

Page 50

Advertising
background image

CHAPTER 5 • SETTINGS 49

˽

Green highlight – This indicates the communication link (port) on which SSMHD is

connected.

˽

RS-485 – Allows you to set the baud rate for RS-485 communication. The Response

Delay setting is used to configure how long the sensor will wait before responding to

a message received. This is useful for some communications devices that are unable to

quickly change transmission direction. The default value is 10 milliseconds.
The Termination checkbox allows you to electronically turn RS-485 communication

bus termination on or off. Only the end devices on a RS-485 bus should be terminated.

In general, the termination can be left unchecked until a multi-drop bus becomes over-

loaded.

˽

RS-232 – Allows you to set the baud rate for RS-232 communication. The Response

Delay setting works the same as the RS-485 section.
The HW Handshaking checkbox should be selected if you are connecting your sensor to

an RS-232 device (such as some modems). These devices sometimes require flow control

handshaking because they cannot keep up with the data rates of higher-performance

devices like personal computers and SmartSensor HD. SmartSensor Manager HD and

SmartSensor HD have built-in support for RS-232 flow control hardware handshaking;

this support allows the SmartSensor HD and SmartSensor Manager HD to work with

these slower modem connections. Table 5.1 gives a brief description of each RS-232 line.

Line

Description

TX

Transmit data line

RX

Data receive line

RTS

Request to send flow control hardware handshaking line

CTS

Clear to send flow control hardware handshaking line

Table 5.1 – RS-232 Lines

In order to use hardware handshaking, the sensor’s RTS and CTS signals must be properly

connected. If the Flow Control option under the Serial connection screen is set to Hard-

ware, you will not be able to connect if the sensor’s HW handshaking setting has been

previously turned off. The reason you cannot connect is that the sensor’s RTS line is not

asserted; as that line is connected to the computer’s CTS line, the computer will not forward

data messages it is given by SmartSensor Manager HD. To successfully connect, simply

change the Flow Control setting to None.

Outputs Tab

The Outputs tab contains the following settings (see Figure 5.4):

Advertising