Safety control drawing, Ratings – Westermo ODW-720-F1 User Manual

Page 6

Advertising
background image

6

6651-2221

FP

Position Descripton

Input / Output values

1

In & out / Relay contact (NO)

U

in

= 60 VDC max

I

in

= 500 mA max

2

In & out / Relay contact (C)

3

In & out / Relay contact (NC)

Galvanically isolated via mechanical relay.

See user manual for proven transient protection.

Position Descripton

Input /Output values

1

Out / Data Carrier Detect (DCD)

U

max

= ± 12 Vpk

I

max

= ± 60 mA

Data rate:
300 bit/s to 250 kbit/s

2

Out / Received Data (RD)

3

In / Transmitted Data (TD)

4

Not connected

5

– / Signal Ground (SG)

6

Out / Data Set Ready (DSR)

7

In / Request To Send (RTS)

8

Out / Clear To Send (CTS)

9

Not connected

Position Descripton

Intput values

1

In / Common

U

in

= (10 – 60) VDC

I

in

= 400 mA max

P

In

= Max 4 W

2

In / +Voltage A

3

In / +Voltage B

4

In / Common

See section Type tests and environmental conditions in this

user manual for proven transient protection.

1234

Safety Control Drawing

Degree of protection

IP 21

Ambient temperature

–40°C to +70°C

Installation spacing

Minimum 25 mm above / below
Minimum 10 mm left / right

Direction relative this unit!

Ratings

Power

(12 – 48) VDC; 300 mA

Ambient temperature

–40ºC ≤ Ta ≤ +70ºC

Ingress protection (IP)

IP21

Maximum surface temperatur 135ºC (temperature class T4)

Position Descripton

Output values

Rx

In / Receive port

Max 0 dBm

Tx

Out / Transmit port

Advertising