2. Run Cycle Sequence (Increasing Load)

• Customer contacts close

Step 1

1. Opstat

4TAS-1

closes as return chilled water temperature starts to rise. Relay

8CR

bypasses pumpdown switch

4PS-1

to remove it from the control circuit.

Note: Go to Step 4 if Compressor 1 is off for more than five (5) minutes.

2. Cycle timer

1TR

times out and closes (up to a five (5) minute delay).

3. Compressor 1 starts. Contactor auxiliary switch energizes liquid line solenoid

1SOL

and

Circuit 1 refrigerant flow starts. Compressor 1 unload solenoid

3SOL

energizes through

4TAS-NC2

and

NC4

. Compressor 1

unloads one bank of cylinders.

4. Oil failure switch

3PS-1

starts to time open (120 sec. delay). Low pressure switch

9PS-1

starts to time open (120 to 240 sec. delay).

Note: If oil pressure or suction pressure is not established at a normal level within the above-

listed delay times, Circuit 1 shuts down.

5. Circuit 1 oil and suction pressure rise to normal levels, and

3PS-1

and

9PS-1

terminate

the time open sequence.

First stage capacity is now on line.

Step 2

6. Opstat

4TAS-2

closes as water temperature continues to rise. Compressor 1 unload

solenoid

1SOL

de-energizes as

4TAS-NC2

opens. Compressor 1 loads up to 100%.

Second stage capacity is now on line.

Step 3

7. Opstat

4TAS-3

closes as water temperature continues to rise. Relay

9CR

bypasses

pumpdown switch

4PS-2

to remove it from the control circuit. Staging timer

4TR-2

delays Compressor 2 start (10 to 30 seconds).

8. Staging timer

4TR-2

closes. If cycle timer

1TR-2

times out, Compressor 2 starts 100%

loaded. Contactor auxiliary switch energizes liquid line solenoid

2SOL

and circuit 2

refrigerant flow starts. Oil Failure switch

3PS-2

starts to time open (120 sec. delay). Low

pressure switch

9PS-2

starts to time open (120 to 240 sec. delay).

Note: If oil pressure or suction pressure is not established at a normal level within previously-

listed delay times, Circuit 2 shuts down.