Figure 19

ACOA Capacity Control




Chiller

model




Comp.

off




Comp. 1

on 33%




Comp. 1

on 50%




Comp. 1

on 66%




Comp. 1

on 100%


Comp. 1

on 50%,

Comp. 2

on 100%


Comp. 1

on 67%,

Comp. 2

on 100%


Comp. 1

and

Comp. 2

on 100%

Comp. 1

on 67%,

Comp. 2 &

Comp. 3

on 100%

Comp. 1,

Comp. 2

& Comp.

3 on

100%

Comp. 1,
Comp. 2,

Comp. 3

& Comp.

4 on

100%


Hot
gas

by-

pass

ACOA15

0

30

100

ACOA20

0

30

100

ACOA25

0

100

ACOA30

0

33

67

100

ACOA35

0

33

67

100

Opt.

ACOA45

0

25

50

75

100

first

ACOA55

0

21

42

78

100

capa-

ACOA70

0

34

50

84

100

city

ACOA80

0

25

50

75

100

step

ACOA90

0

22

33

56

67

89

100

ACOA100

0

22

33

56

67

89

100

ACOA110

0

21

42

71

100

ACOA125

0

25

50

75

100

ACOA135

0

25

50

75

100

Modulates 100% to 30%
Hot gas bypass modulates to approximately half the capacity of the first step.