4. Opstat

4TAS-1

opens as water temperature reaches minimum set point. Liquid line

solenoid

1SOL

de-energizes and Circuit 1 refrigerant flow stops. Relay

8CR

de-

energizes, removing

4PS-1

bypass (

4PS-1

now controls pumpdown). Compressor 1

remains running and Circuit 1 pumpdown begins.

5. When suction pressure drops to the pumpdown limit,

4PS-1

opens and Compressor 1

stops. Circuit 1 pumpdown and unload sequence is now complete, and all Circuit 1
controls are back to standby status.

Figure 11

ACOA Control Settings and Set Points (Unit is Off)

ACOA Control Settings

Time

Delay

1TR-1 & 2

5 Min.

3PS-1 & 2

120 Sec.

9PS-1 & 2

120 Sec.

4TR-2

10 Sec.

5TR-1 & 2

2 Min.

Pressure (PSIG)

Open

Close

1PS-1 & 2

360

10, 11PS-1

140

190

10, 11PS-2

160

21-0

10, 11PS-3

170

230

Temperature

Open

Close

4TAS-1

LWT + .40R

LWT + .55R

4TAS-2

LWT + .55R

LWT + .70R

4TAS-3

LWT + .70R

LWT + .85R

4TAS-4

LWT + .85R

LWT + R

3TAS

40ºF

43ºF

ACOA Set Points

Percentage

of ethylene

Minimum

ambient

Minimum

9PS open

4PS

open

4PS

close

Minimum

2TAS open

glycol

ºF

ºC

psig

kPa

psig

kPa

psig

kPa

ºF

ºC

0%

32ºF

0ºC 55 psig 379 kPa 45 psig 310 kPa 70 psig 483 kPa 38ºF

3ºC

10%

27ºF -3ºC 49 psig 338 kPa 39 psig 269 kPa 64 psig 441 kPa 33ºF

1ºC

20%

18ºF -8ºC 39 psig 269 kPa 29 psig 200 kPa 54 psig 372 kPa 24ºF

-4ºC

30%

3ºF -16ºC 33 psig 228 kPa 23 psig 159 kPa 48 psig 331 kPa

9ºF -13ºC

40%

-13ºF -25ºC 33 psig 228 kPa 23 psig 159 kPa 48 psig 331 kPa -7ºF -22ºC

50%

-20ºF -29ºC 33 psig 228 kPa 23 psig 159 kPa 48 psig 331 kPa -14ºF -26ºC

Caution!

Do not set 9PS, 4PS, or 2TAS lower than indicated for your glycol concentration—

the AEC, Inc. warranty is voided! The AEC, Inc. warranty does not cover freeze-up!

Figure 12

Page 28

ACOA Series Air-Cooled Central Chillers