Encoders

11.1 Error Messages

A: Signal amplitude too low

B: Frequency exceeded
C: Wrong reference mark spacing

x =

CPU number

1

Main processor

2 Geometry processor
3 CLP processor

11.2 Error Causes

Glass scale contaminated or defective
Scanning head contaminated or defective
Cable damaged

Encoder input of the logic unit

defective

11.3 Checking the Encoders

In order to determine whether the encoder or the encoder input of the logic unit is defective, the encoders can
be switched at the logic unit For this purpose, the corresponding machine parameters must be altered as well.

1

Allocation of the axes
to the encoder inputs

X

110.0

Xl

Y

110.1

x2

Z

110.2

x3

IV

110.3

x4

V

110.4

x5
X6*

X6 may only be used for a machine tool axis, if no spindle orientation is required.

Proceeding if error message is displayed

Switch off main switch.

Switch encoder X-axis with e.g. encoder Y-axis at the logic unit.

Switch on main switch.

If the error message POWER INTERRUPTED is generated, call the machine parameters with the code

number 95148 and switch the entry values of the machine parameters 110.0 and 110.1.

Exit the machine parameters and switch on the machine as usual.

If the same error message POWER INTERRUPTED is generated again, the error is located in the encoder or

in the extension cable. If the error message now says

instead of

the encoder input of the logic unit is

defective.