3 connecting speedwire – SMA SI 3.0-11 Installation User Manual

Page 33

Advertising
background image

SMA Solar Technology AG

7  Electrical Connection

Installation Manual

SI30M-44M-60H-80H-IA-en-30

33

Procedure:

1. Insert the data cable in the pin connector Display on the

Sunny Island (see Section 7.5.4 "Connecting the Data Cable",

page 54).

2. Connect the other end of the data cable to the Sunny Remote Control.

7.4.7.2 Connecting the Data Cable of the Lithium-Ion Batteries

Requirement:

☐ The total length of the communication bus must not exceed 30 m. Keep in mind that the communication bus possibly

connects several nodes such as additional Sunny Island inverters.

Cable requirements:

☐ Classification: CAT5e
☐ Type of plug: RJ45

Procedure:

1. Plug the data cable into a free pin connector ComSync on the

Sunny Island. Ensure that the cable is correctly connected

(see Section 7.5.4 "Connecting the Data Cable", page 54).

2. Connect the other end of the data cable to the battery management of the lithium-ion battery (see battery

manufacturer documentation).

3. Ensure that the communication bus is closed at each end, e.g. with a terminator.

7.4.7.3 Connecting Speedwire

Requirement:

☐ A Speedwire data module for Sunny Island must be installed (see the installation manual of the

SMA Speedwire/Webconnect data module).

Cable requirements:

☐ Cable length between two nodes:

– maximum 50 m with patch cable
– maximum 100 m with extension cable

☐ Cross-section: minimum 2 x 2 x 0.22 mm² or minimum 2 x 2 x AWG 24
☐ Cable type: 100BaseTx, CAT5 with shielding S-UTP, F-UTP or higher
☐ Type of plug: RJ45

Advertising
This manual is related to the following products: