5.3 Connection to the Electricity Grid (AC)

5.3.1 Conditions for AC Connection

Cable sizing

Use Sunny Design Version 2.0 or higher for sizing the conductor cross-sections
(see Sunny Design program at www.SMA.de/en).
The maximum cable lengths as a function of conductor cross-section are shown in the following table.

Cable requirements

Connection requirements of the network operator
Always comply with the connection requirements of your network operator.

Cable cross-section

Maximum cable length

WB 3300 / WB 3300-11 /

WB 3300-IT

WB 3800 / WB 3800-11 /

WB 3800-IT

4 mm²

18.5 m

16 m

Object

Description

Value

A

External diameter

6 mm … 14 mm

B

Conductor cross-section

4 mm²

C

Stripping length

8 mm