6 commissioning, 1 commissioning the inverter, Commissioning – SMA WB 3300-11 Installation User Manual

Page 39: Commissioning the inverter

Advertising
background image

SMA Solar Technology AG

Commissioning

Installation Manual

WB33-38-IA-IEN120940

39

6 Commissioning

6.1 Commissioning the Inverter

1. Check the following requirements before commissioning:

– Correct mounting and connection of the inverter.
– Appropriately sized miniature circuit-breaker.
– Correct earthing of the small wind turbine system in accordance with the instructions of the

manufacturer.

– The rectifier and overvoltage protection (e.g. Windy Boy Protection Box) are installed

between the small wind turbine system and the inverter.

– Unused DC inputs are closed with the corresponding DC connectors and sealing plugs

2. Switch on the miniature circuit-breaker.
3. Commission the small wind turbine system in accordance with the instructions of the

manufacturer.
☑ All 3 LEDs on or flashing: the start-up phase commences.
☑ Green LED on: commissioning successful.
or
☑ Green LED flashing: grid connection conditions have not yet been reached. Wait until the

green LED is permanently on.

or
☑ The red or yellow LED lights up or flashes: a disturbance has occurred. Proceed to step 3.

4. Read Section 9 "Troubleshooting" (page 56) and if necessary eliminate the fault or disturbance.

Object

Description

A

Green LED: operation

B

Red LED: earth fault or varistor
defective

C

Yellow LED: disturbance

Self-test in accordance with DK 5940, Ed. 2.2 during initial start-up
(applies to Italy only)
The Italian DK 5940 standard prescribes that an inverter can only operate on the electricity
grid if the disconnection times for overvoltage, undervoltage, minimum frequency and
maximum frequency have been checked.
Start the self-test as described in Section 6.3 "Self-Test in Accordance with DK 5940, Ed.
2.2 (Applies to Italy Only)" (page 41). The test
takes approx. 8 minutes.