Communication cable specifications, Gsd files, Cable requirements – Yaskawa 1000 Series Drive Option - Profibus-DP Technical Manual User Manual

Page 17: Cable length

Advertising
background image

5 Installation Procedure

YASKAWA ELECTRIC

SIEP C730600 42B 1000-Series Option SI-P3 Technical Manual

17

‹

Communication Cable Specifications

To ensure proper performance, Yaskawa recommends using PROFIBUS-DP-dedicated cables that fulfill the
specifications in

Table 6

. Refer to the PROFIBUS-DP website at www.profibus.com for more information on cables.

„

Cable Requirements

Table 6 Communication Cable Requirements

„

Cable Length

Communication speed determines maximum permissible cable length.

Table 7

shows the specifications for Type A bus

cables.

Table 7 Communication Cable Length

‹

GSD Files

To facilitate network implementation, obtain a GSD file from one of the following websites depending on your region:
US: http://www.yaskawa.com
Europe: http://www.yaskawa.eu.com
Japan: http://e-mechatronics.com
Other areas: Contact your Yaskawa representative

Condition

Specifications

Impedance

135 to 165

Ω at a frequency of (3 to 20 MHz)

Capacity

30 pF/m maximum

Loop Resistance

110

Ω/km maximum

Core Cross-Section

0.34 mm

2

minimum

Core Diameter

0.64 mm minimum

Communication Speed (kbps)

Distance per Segment

9.6

1200 m (3937 ft.)

19.2

1200 m (3937 ft.)

45.45

1200 m (3937 ft.)

93.75

1200 m (3937 ft.)

187.5

1000 m (3280 ft.)

500

400 m (1312 ft.)

1500

200 m (656 ft.)

3000

100 m (328 ft.)

6000

100 m (328 ft.)

12000

100 m (328 ft.)

Advertising