Example: to read current ppo-write – Yaskawa 1000 Series Drive Option - Profibus-DP Technical Manual User Manual

Page 34

Advertising
background image

8 Parameter Process Data Object Formats

34

YASKAWA ELECTRIC SIEP C730600 42B 1000-Series Option SI-P3 Technical Manual

Response

„

Example: To read the data Type 1 PPO-Write 1st word

Command setting

Response

„

Example: To read current PPO-Write

Command setting

Response

PWE

0

N/A

STW

up to Master command

HSW

up to Master command

Data type

Settings

Description

PKE

438BH

4: Transfer parameter value (array word)
38BH=907 dec (PNU 907)

IND

5

5th Word data of PPO type 1

PWE

(ZSW)

ZSW data

ZSW

up to drive status

HIW

up to drive status

Data type

Settings

Description

PKE

6384H

6: Request parameter value from array
384H=900 dec (PNU 900)

IND

1

First Word data of PPO type 1

PWE

0

N/A

STW

up to Master command

HSW

up to Master command

Data type

Settings

Description

PKE

4384H

4: Transfer parameter value (array word)
384H=900 dec (PNU 900)

IND

1

First Word data of PPO type 1

PWE

6384H

PPO-Write 1st Word data

ZSW

up to drive status

HIW

up to drive status

Data type

Settings

Description

PKE

1388H

1: Request parameter value
388H=904 dec (PNU 904)

IND

0

Not array type

PWE

0

N/A

STW

up to Master command

HSW

up to Master command

Data type

Settings

Description

PKE

1388H

1: Transfer parameter value (word)
388H=904 dec (PNU 904)

IND

0

Not array type

PWE

1

1: Type 1 PPO-Write
2: Type 2 PPO-Write
3: Type 3 PPO-Write
4: Type 4 PPO-Write
5: Type 5 PPO-Write

ZSW

up to drive status

HIW

up to drive status

Data type

Settings

Description