B parameter table – Yaskawa L1000E AC Drive CIMR-LE†A User Manual

Page 212

Advertising
background image

B Parameter Table

212

YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

U3: Fault History

U4: Maintenance Monitors

No.

(Addr.)

Name

Description

Analog Output

Level

Unit

U3-01 to

U3-04

(90H to

93H

(800H to

803H))

First to 4th Most Recent
Fault

Displays the first to the fourth most recent faults.

No signal output
available

U3-05 to

U3-10

(804H to

809H)

5th to 10th Most Recent
Fault

Displays the fifth to the tenth most recent faults.
After ten faults have occurred in the drive, data for the oldest fault is deleted.
The most recent fault appears in U3-01, with the next most recent fault
appearing in U3-02. The data is moved to the next monitor parameter every
time a fault occurs.

No signal output
available

U3-11 to

U3-14

(94H to

97H

(80AH to

80DH))

Cumulative Operation
Time at 1st to 4th Most
Recent Fault

Displays the cumulative operation time when the first to the fourth most recent
faults occurred.

No signal output
available

1 h

U3-15 to

U3-20

(80EH to

813H)

Cumulative Operation
Time at 5th to 10th Most
Recent Fault

Displays the cumulative operation time when the fifth to the tenth most recent
faults occurred.

No signal output
available

1 h

No.

(Addr.)

Name

Description

Analog Output

Level

Unit

U4-01

(4CH, 98H,

99H)

<41>

Cumulative Operation
Time

Displays the cumulative operation time of the drive. The value for the
cumulative operation time counter can be reset in parameter o4-01. Use
parameter o4-02 to determine if the operation time should start as soon as the
power is switched on or only while the Up/Down command is present. The
maximum number displayed is 99999, after which the value is reset to 0.

No signal output
available

1 h

U4-03

(67H, 94H,

9BH)

<42>

Cooling Fan Operation
Time

Displays the cumulative operation time of the cooling fan. The default value
for the fan operation time is reset in parameter o4-03. This value will reset to 0
and start counting again after reaching 99999.

No signal output
available

1 h

U4-04
(7EH)

Cooling Fan
Maintenance

Displays main cooling fan usage time in as a percentage of its expected
performance life. Parameter o4-03 can be used to reset this monitor. The fan
should be replaced when this monitor reaches 90%.

No signal output
available

1%

U4-05
(7CH)

Capacitor Maintenance

Displays main circuit capacitor usage time in as a percentage of their expected
performance life. The capacitors should be replaced when this monitor reaches
90%. Parameter o4-05 can be used to reset this monitor.

No signal output
available

1%

U4-06

(7D6H)

Soft Charge Bypass
Relay Maintenance

Displays the soft charge bypass relay maintenance time as a percentage of its
estimated performance life. The soft charge relay should be replaced when this
monitor reaches 90%. Parameter o4-07 can be used to reset this monitor.

No signal output
available

1%

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_