Yaskawa GPD505/P5 User Manual

Page 31

Advertising
background image

27

TM.IW.01

Parameter Name

Function

Range/Scale

Comment

Frequency Reference

Main frequency reference inside
inverter

0 – max Hz

Output Frequency

Inverter output frequency (U-02)

0 – max Hz

Output Current

Inverter output amps

0 – 200% Inv Rated Not amps but %

Output Voltage

Inverter output voltage

0 – 250 VAC

400 V & 600V reads in
200 V scale only

DC Bus Voltage

Inverter DC Bus Voltage

0 – 400 VDC

400 V & 600V reads in
200 V scale only

DI Input byte

Status of terminal S1 – S6 (U-
07)

0 - 63

Decimal of bits 0 - 5

Inv Status Byte

Inverter status bits (U 08)

0 - 256

Decimal of bits 0 - 7

Elapsed Time (Min)

Elapsed time monitor in minutes

0 -65535

PID Feedback

Value of PID feedback (U-13)

0 – 60 HZ

60 Hz = 100%

Kwh Monitor

Kilowatt hour monitor

0 - 65535

S6 Closed

Status of S6

0 - 1

1 = Closed (ON)

S5 Closed

Status of S6

0 - 1

1 = Closed (ON)

S4 Closed

Status of S6

0 - 1

1 = Closed (ON)

S3 Closed

Status of S6

0 - 1

1 = Closed (ON)

S2 Closed

Status of S6

0 - 1

1 = Closed (ON)

S1 Closed

Status of S6

0 - 1

1 = Closed (ON)

Run bit

Status of S6

0 - 1

1 = Closed (ON)

Reverse Run bit

Status of S6

0 - 1

1 = Closed (ON)

Inverter Ready Bit

Status of S6

0 - 1

1 = Closed (ON)

Inv Fault Bit

Inverter Fault Bit

0 –1

MODBUS Write Error

MODBUS Parameter Write error

0 -FFFFh

Parameter Address

MA –MC Closed

Status of MA-MC contact

0 -1

M1-M2 Closed

Status of M1-M2 contact

0 -1

Fault and Alarm bits

Bit status

0 -1

See program for list

Table 3.15: Monitor parameter selections