Table 4.3 G7 Monitor Registers (Read only)

U-## Addr.

Function

Bit

Description

U1-15

004Eh

Analog Input Terminal A1 Level

-

Units 0.1%

U1-16

004Fh

Analog Input Terminal A2 Level

-

Units 0.1%

U1-17

0050h

Analog Input Terminal A3 Level

-

Units 0.1%

U1-18

0051h

Motor Secondary Current (Iq)

-

Units 0.1%

U1-19

0052h

Motor Excitation Current (Id)

-

Units 0.1%

U1-20

0053h

Frequency Reference After Soft Starter

-

Units 0.01Hz

U1-21

0054h

ASR (Speed Regulator) Input

-

Units 0.01%

U1-22

0055h

ASR (Speed Regulator) Output

-

Units 0.01%

U1-24

0057h

PID Feedback

-

Units 0.01%

U1-25

0058h

DI-16H2 Reference

-

Scaling Dependent Upon F3-01 Setting

U1-26

0059h

Voltage Reference (Vq)

-

Units 0.1VAC

U1-27

005Ah

Voltage Reference (Vd)

-

Units 0.1VAC

U1-28

005Bh

Drive CPU Number

-

Last 5 Digits of CPU Software Number

U1-29

005Ch

Accumulated kWh

-

Units 1.0kWh

U1-30

005Dh

Accumulated MWh

-

Units 1.0MWh

U1-32

005Fh

ACR (q) Output

-

Units 0.1%

U1-33

0060h

ACR (d) Output

-

Units 0.1%

U1-34

0061h

First Parameter Causing an OPE Fault

-

Modbus Address of Parameter Causing OPE Fault

U1-35

0062h

Zero Servo Pulse Count

-

Units are Quadrature Pulse Counts

U1-36

0063h

PID Input

-

Units 0.01%

U1-37

0064h

PID Output

-

Units 0.01%

U1-38

0065h

PID Setpoint

-

Units 0.01%

0 CRC

Error

1

Data Length Error

2 Reserved

3 Parity

Error

4 Over-run

Error

5 Framing

Error

6 Timeout

Error

U1-39

0066h

Communication Error Code

7h-Fh Reserved

U1-40

0067h

Heatsink Cooling Fan Operation Time

-

Units 1.0hr

U1-42

0069h

Estimated Motor Flux

-

Units 0.1%

U1-43

006Ah

Motor Flux Compensation

-

Units 0.1%

U1-44

006Bh

ASR Output Without Filtering

-

Units 0.01%

U1-45

006Ch

Feed Forward Control Output

-

Units 0.01%

U1-48

006Fh

Stabilizing Speed During Regeneration

(Open Loop Vector 2 Only)

- Units

0.1Hz

U1-50

0070h

CF Error

(Open Loop Vector 2 Only)

-

00: Deceleration Error

01: Flux estimation fault

02: Start status error

04: Observer gain adjustment error

08: Regeneration error at low speeds

10: Zero Speed error

20: Rotational direction limit error

80: Vector control status error

U1-90

0720h

CASE Monitor 1

-

Custom Units - Refer to Specific CASE Software Documentation

U1-91

0721h

CASE Monitor 2

-

Custom Units - Refer to Specific CASE Software Documentation

U1-92

0722h

CASE Monitor 3

-

Custom Units - Refer to Specific CASE Software Documentation

U1-93

0723h

CASE Monitor 4

-

Custom Units - Refer to Specific CASE Software Documentation

U1-94

0724h

CASE Monitor 5

-

Custom Units - Refer to Specific CASE Software Documentation

U1-95

0725h

CASE Monitor 6

-

Custom Units - Refer to Specific CASE Software Documentation

U1-96

0726h

CASE Monitor 7

-

Custom Units - Refer to Specific CASE Software Documentation

U1-97

0727h

CASE Monitor 8

-

Custom Units - Refer to Specific CASE Software Documentation

U1-98

0728h

CASE Monitor 9

-

Custom Units - Refer to Specific CASE Software Documentation

U1-99

0729h

CASE Monitor 10

-

Custom Units - Refer to Specific CASE Software Documentation

U2-01

0080h

Current Fault

-

See Table 4.17

U2-02

0081h

Previous Fault

-

See Table 4.17

U2-03

0082h

Frequency Reference at Previous Fault

-

Units 0.01Hz

U2-04

0083h

Output Frequency at Previous Fault

-

Units 0.01Hz