Yaskawa G7 Modbus Communication User Manual

Page 88

Advertising
background image

88

Table 5.1 User Parameter Settings

Parameter

Description

Default

User Setting

Notes

H4-02

Terminal FM Gain

100.00 %

H4-03

Terminal FM Bias

0.00 %

H4-04

Terminal AM Selection

03h

H4-05

Terminal AM Gain

50.00 %

H4-06

Terminal AM Bias

0.00 %

H4-07

Terminal FM Signal Type

0

H4-08

Terminal AM Signal Type

0

H5-01

Modbus Node Address

1fh

H5-02 Baud

Rate

3

H5-03 Parity

Selection

0

H5-04

Communication Loss Response

3

H5-05

Communication Fault Selection

1

H5-06

Transmit Wait Time

5 ms

H5-07 RTS

Control

Selection

1

H5-10

Unit Selection for Register 0025h

0

H6-01

Terminal RP Selection

0

H6-02

Terminal RP Scaling

1440 Hz

H6-03

Terminal RP Gain

100.00 %

H6-04

Terminal RP Bias

0.00 %

H6-05

Terminal RP Filter Time

0.10 Sec

H6-06 Terminal

MP

Selection

02h

H6-07

Terminal MP Scaling

1440 Hz

L1-01

Motor Overload Fault Selection

1

L1-02

Motor Overload Time Constant

1.0 min

L1-03

Motor OH Alarm Selection

3

L1-04

Motor OH Fault Selection

1

L1-05

Motor Temperature Filter Time

0.20 Sec

L2-01

Power Loss Ride Thru Selection

0

L2-02

Power Loss Ride Thru Time

0.1 Sec

L2-03

Minimum Baseblock Time

0.5 Sec

L2-04

Voltage Recovery Ramp Time

0.3 Sec

L2-05

Undervoltage Detection Level

kVA Dep.

L2-06

KEB Decel Time

0.0 Sec

L2-07

Power Loss Accel Time

0.0 Sec

L2-08

KEB Frequency Gain

100 %

L3-01

Stall Prevention Accel Selection

1

L3-02

Stall Prevention Accel Level

150 %

L3-03

Stall Accel Const HP Level

50 %

L3-04

Stall Prevention Decel Selection

1

L3-05

Stall Prevention Run Selection

1

L3-06

Stall Prevention Run Level

160 %

L3-11

Overvoltage Inhibit Selection

0

L3-12

Overvoltage Inhibit Voltage

Level

kVA Dep.

L4-01

Speed Agree Level

0.0 Hz

L4-02

Speed Agree Width

2.0 Hz

L4-03

Speed Agree Level +/-

0.0 Hz

L4-04

Speed Agree Width +/-

2.0 Hz

L4-05

Frequency Reference Loss Select

0

L4-06

Frequency Reference Loss Gain

80.00 %

L5-01

Number of Auto-Restarts

0

L5-02

Fault Selection During Restart

0

L6-01

Torque Detection 1 Selection

0

L6-02

Torque Detection 1 Level

150 %

L6-03

Torque Detection 1 Time

0.1 Sec

L6-04

Torque Detection 2 Selection

0

L6-05

Torque Detection 2 Level

150 %

L6-06

Torque Detection 2 Time

0.1 Sec

L7-01

Torque Limit Forward Motoring

200 %

Advertising