69

Table 4.11 “L” Parameters

Access Level

Name

Address

Description

Data

Range

Unit

Default

During

Run

V/f

V/f

w/PG

OLV

FV

OLV2

L5-01

049Eh

Number of Auto-Restarts

0 ~ 10

1

0

A

A

A

A

A

0

No Fault Relay

L5-02

049Fh

Fault Selection During

Auto-Restart

1

Fault Relay Active

1

0

A A A A A

0 Disabled

1

Overtorque, Speed Agree,

Alarm

2

Overtorque, Run, Alarm

3

Overtorque, Speed Agree,

Fault

4

Overtorque, Run, Fault

5

Undertorque, Speed Agree,

Alarm

6

Undertorque, Run, Alarm

7

Undertorque, Speed Agree,

Fault

L6-01

04A1h

Torque Detection 1

Selection

(OL3, UL3)

8

Undertorque, Run, Fault

1

0

A A A A A

L6-02

04A2h

Torque Detection 1

Level

0 ~ 300 %

1 %

150 %

A

A

A

A

A

L6-03

04A3h

Torque Detection 1 Time

0.0 ~ 10.0 Sec

0.1 Sec

0.1 Sec

A

A

A

A

A

0 Disabled

1

Overtorque, Speed Agree,

Alarm

2

Overtorque, Run, Alarm

3

Overtorque, Speed Agree,

Fault

4

Overtorque, Run, Fault

5

Undertorque, Speed Agree,

Alarm

6

Undertorque, Run, Alarm

7

Undertorque, Speed Agree,

Fault

L6-04

04A4h

Torque Detection 2

Selection

(OL4, UL4)

8

Undertorque, Run, Fault

1

0

A A A A A

L6-05

04A5h

Torque Detection 2

Level

0 ~ 300 %

1 %

150 %

A

A

A

A

A

L6-06

04A6h

Torque Detection 2 Time

0.0 ~ 10.0 Sec

0.1 Sec

0.1 Sec

A

A

A

A

A

L7-01

04A7h

Torque Limit Forward

Motoring

0 ~ 300 %

1 %

200 %

A

A

A

L7-02

04A8h

Torque Limit Reverse

Motoring

0 ~ 300 %

1 %

200 %

A

A

A

L7-03

04A9h

Torque Limit Forward

Regeneration

0 ~ 300 %

1 %

200 %

A

A

A

L7-04

04AAh

Torque Limit Reverse

Regeneration

0 ~ 300 %

1 %

200 %

A

A

A

L7-06

04ACh

Torque Limit Filter Time

5 ~ 10000 ms

1 ms

200 ms

A

0 P

Control

L7-07

04C9h

Torque Limit Control

Selection During

Accel/Decel

1 PI

Control

1

0 A

0 Not

Provided

L8-01

04ADh

Dynamic Braking

Resistor Protection

Selection

(Only for Yaskawa 3%

heatsink mounted

resistors)

1 Provided

1

0

A A A A A

L8-02

04AEh

Overheat (OH)

Pre-Alarm Level

50 ~ 130 Deg

1 Deg

95 Deg

A

A

A

A

A

0

Ramp to Stop

1

Coast to Stop

2 Fast-Stop

(C1-09)

L8-03

04AFh

Overheat (OH) Pre-

Alarm Selection

3 Alarm

Only

1

3

A A A A A

0 Disabled

L8-05

04B1h

Input Phase Loss (PF)

Selection

1 Enabled

1

0

A A A A A

0 Disabled

L8-07

04B3h

Output Phase (LF) Loss

Method Selection

1

1 Phase Loss Detection

1

0

A A A A A