Troubleshooting

34

4.3

Module Replacement

Follow the instructions below when replacing or

adding a Control, Battery or Power Module to the

system.
To order additional modules, contact your Liebert

representative or call 1-800-LIEBERT.

4.3.1 Removing Modules

1. Remove bezel cover of appropriate module.

When replacing a Power or Battery Module,

verify the faulty module by confirming the

yellow LED is lit.

2. If removing a Control or Power Module with

no redundant modules, switch UPS to

manual bypass.

3. Pull out and lift the lever if replacing a

Control or Power Module, then turn fastener

counterclockwise until it is loosened.

4. To remove the module:

a. Start to pull out module (shown above

right, top). About 2/3 out it will stop.

b. Slide module away from the center of the

UPS (shown above right, center).

c. Continue to pull until module is removed

(shown above right, bottom).

5. Dispose of module in an environmentally

responsible way that complies with local

codes/regulations or return to Liebert for

proper disposal.

!

CAUTION

Battery Modules are heavy—66 lb (30 kg).

NOTE
Battery Modules may contain shipping

screws. These screws may be removed and

discarded.

WARNING

POTENTIAL TIP HAZARD

Install all battery modules starting from
the bottom. For module removal, start
from the top. Do not remove more than
one module at a time. Failure to do so
may cause unit to tip over and cause
serious injury.

Step 4a

MODULE REMOVAL

(Steps 4a-c)

Step 4b

Step 4c

Turn fastener

counterclockwise

Lift lever up (for

Control and Power Modules)