3 rmcc controllers, 4 mrlds modbus version (809-101x), 1 network layout – Emerson MRLDS User Manual

Page 11: 2 mrlds setup, 1 mrlds wiring, 2 mrlds network addressing, Etwork, Ayout, 2 mrlds s, Etup

Advertising
background image

Network Layout

MRLDS Modbus Version (809-101x)

5

3.4.3

RMCC Controllers

For RMCC-type controllers, set the Gain parameter to

250 and Offset to -1000.

4

MRLDS Modbus

Version (809-101x)

4.1

Network Layout

4.2

MRLDS Setup

4.2.1

MRLDS Wiring

4.2.2

MRLDS Network Addressing

Modbus network settings are set on jumpers J5, J4,

and J3. Refer to Table 4-1 (also included on the inside
label of the MRLDS) for network addressing with corre-
sponding jumper settings.

If more than one MRLDS is on the network, each unit

must have a unique address and be numbered according to
the inside label (Table 4-1) specifications.

Figure 3-4

- Analog Input Screen Settings Example for E2

Figure 4-1

- Network Layout Example

E2

Gateway

MRLDS

MRLDS

MRLDS

MRLDS

I/O Net

+

-

+

-

-

-

-

-

+

+

+

+

MODBUS

(Up to 12 MRLDS
units on the network
per Gateway)

Figure 4-2

- Modbus MRLDS Wiring

Figure 4-3

- MRLDS Jumpers (Inside Lower Portion of Cover)

R

S

4

8

5

(

+

)

R

S

4

8

5

(-

)

A

C

N

2

4

V

A

C

MRLDS - INSIDE LOWER
PORTION OF BASE

E

A

R

T

H

G

N

D

Shield
drain/ground
wire

MODBUS
NETWORK

To Gateway
Board

A transformer must

be shared

between MRLDS
and the Gateway
board. A

must

be used.

If a transformer is
shared between
MRLDS units,
the “ACN” of
each MRLDS
must be wired
to the same
phase of the
transformer.

never

separate

transformer

MODBUS

BELDEN
8761

14 AWG less
than 6 inches

J6 J5 J4 J3 J2 J1

refrigerant
type
jumpers

network
address
jumpers

term
jumper

J6

J1

Advertising