1 overview, 1 specifications, 2 mrlds models – Emerson MRLDS User Manual

Page 7: 3 powering the mrlds, 2 mrlds m, Odels, Owering, Mrlds, 1overview, 2 mrlds models 1.3 powering the mrlds

Advertising
background image

Specifications

Overview

1

1

Overview

CPC specs a modular refrigerant leak detection sensor

(MRLDS) that continuously monitors for low levels of
refrigerants most commonly used in commercial refrigera-
tion systems.

The MRLDS communicates with the E2 controller via

a Gateway board connected to the RS485 I/O Network, or
via the analog input on a MultiFlex board.

1.1

Specifications

*De-icer: for environments below 32°F to keep ice from

forming on the surface of enclosure.

1.2

MRLDS Models

1.3

Powering The MRLDS

The MRLDS unit requires a separate UL Listed/CSA

Certified 24VAC Class 2 transformer power supply. One
24VAC, 10VA Class 2 transformer is sufficient for up to
three (3) MRLDS units.

CPC supplies several sizes of transformers for power-

ing multiple MRLDS units (three or more). Note that
polarity must be maintained when connecting more than
one MRLDS to a single transformer.

Power Require-
ments

24 VAC, ±20%, 50/60 Hz, Class 2

Wiring

14 AWG max, Class 2 copper wir-
ing

Power Consump-
tion

Less than 2.7 watts

Output Options

1-5V, 10 K Ohm load

RS485 Modbus RTU

Operating Temp.

32 to 149°F (-22 to 149°F with
de-icer*)

0 to 65°C (-30 to 65°C with
de-icer*)

Humidity

0 to 99% non-condensing

Size

4.5” x 3.5” x 1.6”

Weight

.35 lbs. (160 g)

Pollution Degree

2

Installation Cate-
gory

II

Range

0 to 1000 ppm

Minimum Detec-
tion

25 ppm

Pressure

Operating 10.2 to 15.7 PSIA

Repeatability

±10 ppm at 50 ppm

Linearity

±10 ppm from 25-50 ppm,

±20% of reading from 60 to 1000
ppm

Warm-up Time

30 minutes

Table 1-1

- MRLDS Unit Specifications

Figure 1-1

- Sensor Base Opening With Screw Terminals

Part Number

Description

809-1000

Voltage Out w/o de-icer*

809-1001

Voltage Out w/ de-icer*

809-1010

Modbus w/o de-icer*

809-1011

Modbus w/ de-icer*

Table 1-2

- Available MRLDS Models

Part Number

Transformer

Description

Number of

MRLDS Units

Powered

640-0039

24VAC, 10VA

Class 2

Up to 3

Table 1-3

- MRLDS Transformer Specifications

WARNING: The MRLDS unit must be always
be powered by either a suitable UL 60950/CSA
Certified power supply that is isolated from line

voltage by double insulation, or an appropriately rated
UL Listed/CSA Class 2 transformer. Failure to follow
the above can result in serious personal injury or death.