MRLDS I&O Manual

026-1307 Rev 1 11-30-07

ways.

Navigate to the controller’s Input Status screen and

highlight the board and point that you wish to map. Press
F1 to go to the Input Setup screen for that board/point.
Each point will increase incrementally to correspond with
each board. (For example, where the MRLDS is address 1
and the MRLDS address is 100, use board 1, point 1. For
an MRLDS address of 101, use point 2.
)

4.4.3

E2/Einstein Controllers

Next, set up the following parameters on the Input

Setup screen:

• Sensor Type: Linear

• Low End Point: 0.00000

• Select Eng. Units: PPM

• HighEnd Point: 4.80000

• High Eng. Units: 1200.0000

4.4.4

RMCC Controllers Version

2.1 and Newer

4.4.4.1

REFLECS Setup for IRLDS IIs

Set dip switch 8 to ON and follow the steps for setting

up IRLDS IIs through the REFLECS controller interface:

1.

Log on.

2.

Press 7 for Configuration to reach the CON-
FIGURATION
screen.

Input Definitions should be set here to show how the

sensor control is linked to the zone. The number of devices
and IRLDS IIs are connected to the Gateway and enabled
is the number of address slots the Gateway will use.

3.

Press 1 for Input Definitions to reach the
INPUT DEFINITIONS screen.

4.

Pressing the down arrow several times will
get you to the input list of SENS01-48. Bd
(board) is the address of the Gateway, Pt
(point) is the zone and allows you to define
where the sensor input comes from.

The board number for the IRLDS II setup is the address

of the Gateway. If there are three or less IRLDS II control-
lers connected to a Gateway, the Gateway address = the
IRLDS II address. However, if there are more than three
IRLDS controllers, the second Gateway address will be the
one entered for the board number, but the IRLDS II con-
trollers are set 1 to 3 on the second Gateway.

5.

Press 0 (zero) to go back to the CONFIGU-
RATION
screen.

6.

Press 7 for I/O Brd Setup to reach the I/O
BOARD MENU
screen.

7.

Press 2 to Set Device #’s.

The Gateway will react as three 16AI boards. The num-

ber of IRLDS II controllers plus the real number of 16AIs
= the total number of 16AIs to enter in the next step:

8.

At the I/O BOARD DEVICE NUMBERS
screen, press the down arrow key to reach
Number 16AI Boards and enter the number
of how many 16AI boards and IRLDS II con-
trollers there are. Press Enter.

9.

Arrow down to the I/O BOARD MENU and
press 0 (zero) twice to go back to the MAIN
MENU
screen.

10. Press 4 for Sensor Control.

11. Press 2 for Setup--up to 48 sensor control

programs are allowed. Select one of the 48
units and press Enter to reach the SENSOR
SETUP
screen.

12. Press the right arrow to move to the Name

Figure 4-20

- Analog Input Screen Settings Example for E2