7 termination settings, 8 gateway board i/o net addressing, Figure 4-10 – Emerson MRLDS User Manual

Page 15: Figure 4-11, Figure 4-12, Connecting the gateway to the e2 rs485 network, Connecting the gateway to modbus, Mrlds gateway termination, Network layout example

Advertising
background image

MRLDS Gateway

MRLDS Modbus Version (809-101x)

9

controller’s user manual.

To connect the Gateway to an MRLDS, feed the wires

through the rectangular opening in the sensor base as indi-
cated in Figure 1-1. Locate the RS485 connector and
secure the wire leads to the connector orienting them as
shown in Figure 4-10. Connect multiple MRLDS units in
a daisy-chain configuration as shown in Figure 4-1.

4.3.7

Termination Settings

As part of a site controller’s RS485 I/O (COM A or

COM D) Network, a Gateway must be terminated if it is
the end device of a daisy chain. The Gateway on the Mod-
bus Network should always be terminated and always
located at the end of the daisy chain.

Refer to the site controller’s user manual for informa-

tion about daisy chain networks and how they are termi-
nated.

To terminate the Gateway (the Modbus jumpers should

always be terminated on the Gateway), set the receiver bus
jumpers to the RIGHT position (Figure 4-11).

4.3.8

Gateway Board I/O Net

Addressing

Set the address on the I/O Network with switches 1-4.

There can be more than one MRLDS Gateway with each
supporting up to 12 MRLDS units.

Switch 5 indicates whether the MRLDS will be

mapped as an IRLDS or 16AI. Set switch 5 to the OFF
position for IRLDS emulation or to the ON position for
16AI emulation.

Figure 4-9

- Connecting the Gateway to the E2 RS485 Network

Figure 4-10

- Connecting the Gateway to MODBUS

GATEWAY BOARD

-485

+485

0v

To MRLDS
MODBUS

A

B

R

S

4

8

5

+

R

S

4

8

5

-

A

C

N

2

4

V

A

C

MRLDS - INSIDE LOWER
PORTION OF BASE

GATEWAY BOARD

+485

-485

0v

+485

-485

0v

E

A

R

T

H

G

N

D

Shield
drain/ground
wire

Shield drain/
ground
wire

MODBUS
NETWORK

Figure 4-11

-MRLDS Gateway Termination

Figure 4-12

- Network Layout Example

RS485
I/O NET
(TO CPC
CONTROLLER)

RS485 I/O NET

TERM JUMPERS

TERMINATION

(ALWAYS
TERMINATE)

14

15

ADDRESS ON
I/O NET

I/O NET MODE
ON = 16AI
OFF = IRLDS