Code press code 123 press – Energizer ATX612 User Manual

Page 11

Advertising
background image

16

17

CODE

PRESS

CODE 123

PRESS

• Press (+) to step to the INSTANT function and set

instantaneous alarm values. The display will indicate
INSTANT along with the scrolling prompt PRESS (+)
FOR NEXT (E) TO SELECT.

• Press (E) to enter the instantaneous alarms function. The

display will show the first alarm to be set along with the
scrolling prompt PRESS (+) FOR NEXT (E) TO
SELECT. The alarm type will be indicated on the display
as either high (H) or low (L).

• Press (E) to select the desired alarm to be changed. The

display will flash the current alarm value along with the
prompt PRESS (+) OR (-) TO SET (E) TO SELECT.

• Press the (+) and (-) keys to set the desired alarm value

and (E) to enter the value into memory.

• Press MODE to return to the INSTANT function.

• Press (+) to step to the TWA and STEL alarm functions.

The TWA and STEL alarm values are set as
previously described.

6.3 C

ODE

The CODE function allows the user to select a security
code to protect calibration and all instrument alarm
settings. When the code is set to any value other than “0”,
the user will be prompted to enter the proper code prior to
entering the settings or calibration modes.

• Press (+) to step from the ALARMS function to the

CODE function.

• Press (E) to enter the code function. The display will

show the current code setting along with the scrolling
prompt PRESS (+) OR (-) TO SET (E) TO ENTER.

• Press the (+) and (-) keys to set the code to any value

between 0 and 999, and (E) to enter the value
into memory.

• Press MODE to return to the CODE function.

7.

H

YGIENE

/D

ATALOGGING

F

UNCTIONS

7.1 D

EFINITION

O

F

T

ERMS

7.1.1

DATA LOG

The record of measured gas concentrations, including time
and date, stored in the instrument’s electronic memory.

LEL

PRESS

25

LEL

PRESS

ALARMS

PRESS

LATCH

INSTANT

PRESS

10L LEL

PRESS

LATCH

PRESS

OFF

PRESS

• Press (E) to enter the SETSPAN function. The display

will show LEL along with the prompt PRESS (+) TO
CHANGE.

• Press (+) to toggle between LEL and CH

4

combustible

sensor span ranges.

Press MODE to enter the calibration gas values for all

sensors. The display will show the first span value, eg.
25 LEL, along with the prompt PRESS (+) FOR NEXT
(E) TO SELECT.

• Press (E) to select the value you wish to change. The

display will flash the current gas value and will scroll the
prompt PRESS (+) or (-) TO SET (E) TO ENTER.

• Press the (+) and (-) minus keys to set the desired

calibration gas value and (E) to enter the value into
memory. Once the value has been entered into memory,
it will become the standard gas value used during
instrument calibration.

• Press the MODE switch to return to the SETSPAN

function.

6.2 A

LARMS

The ALARMS function allows you to set the values for
the HI and LOW alarms for each installed sensor. Default
alarm settings for each gas are listed in Section 11. If the
hygiene/datalogging option is installed, you will also be
able to set the STEL and TWA alarm values.

• Press (+) to step from the SETSPAN function to the

ALARMS function.

• Press (E) to enter the ALARMS function. The LATCH

function will lock the alarm indicators on when a
monitored gas concentration reaches the high alarm
setpoint. The alarm will reset after the gas concentration
has fallen below the alarm setpoint and the user has
pressed the (E) key. The display will indicate LATCH
along with the scrolling prompt PRESS (+) FOR NEXT
(E) to SELECT.

• Press (E) to select the LATCH function. The display will

indicate LATCH along with the prompt PRESS (+) FOR
NEXT (E) TO SELECT.

• Press (E) to set the ATX612 high alarm latch as ON or

OFF. Press MODE to return to the LATCH screen.