1420 wireless gateway – Emerson Process Management Wireless Gateway 1420 User Manual

Page 10

Advertising
background image

Quick Installation Guide

00825-0100-4420, Rev CA

June 2007

1420 Wireless Gateway

10

S

TEP

4: M

OUNT

AND

C

ONNECT

THE

1420

Integral Antenna with the 1420 on a Mast

The optimal installation of the 1420 Wireless Gateway is
on a pole approximately 1.8 meters above the top of the
exterior wall of a building. The following hardware and
tools are needed:

• Pipe mount with holes spaced 3.06 inches (78 mm)

apart horizontally and 11.15 inches (283 mm) apart
vertically.

• Two 3.06 inch (78 mm) by

5

/

16

inch U-bolts

1

/

2

inch wrench

Mount the gateway by doing the following:

1. Insert one U-bolt around the pipe and through the

top mounting holes of the pipe mount and the 1420,
and another U-bolt through the bottom mounting
holes of the pipe mount and the 1420.

2. Using a

1

/

2

inch socket-head wrench, fasten the nuts

to the U-bolts and tighten.

BEST PRACTICE
When mounting outside, best practice is to run the
Serial or primary Ethernet cable (P1) directly to the
Information System. Use conduit and/or strain relief
as necessary.

BEST PRACTICE
When installing cable/conduit, run an ethernet
connection from 1420 port P2 to a convenient
location indoors (if the 1420 was ordered with
Output Code 2). This will simplify future
configuration changes.

1.8 m (6 ft.)

Strain
Relief

1420_QIG_Rev_CA.fm Page 10 Thursday, June 7, 2007 1:18 PM