1420 wireless gateway – Emerson Process Management Wireless Gateway 1420 User Manual

Page 13

Advertising
background image

Quick Installation Guide

00825-0100-4420, Rev CA
June 2007

1420 Wireless Gateway

13

Canadian Standards Association (CSA)

N6 CSA Division 2 & Dust Ignitionproof

Certificate Number: See Certificate
Suitable for Class I, Division 2, Groups A,B,C,D;
Dust Ignitionproof for Class II, Groups E,F, and G;
Suitable for Class III Hazardous Locations.
Install per Rosemount drawing 01420-1011.
Temperature Code: T4 (-40°C < T

a

< 60°C)

CSA Enclosure Type 4XEuropean Certification

European Certification

N1 CENELEC Type n (ATEX)

See note below
Certificate Number: See Certificate
ATEX Marking: Ex II 3 G
EEx nA nL IIC T4 (-40°C < T

a

< 60°C)

ND ATEX Dust Ignition-proof Approval

Certificate Number: See Certificate
Ex tD A22 IP66 T135 (-40

°C< Ta < +60

EEx nA nL IIC T4 (-40°C < T

a

< 60°C)

II 3D

Vmax = 28V

IECEx Certification

N7 IECEx Type n

See note below
Certificate Number: See Certificate
Ex nC IIC T4 (-40°C =< T

a

<= +60°C)

Rated Voltage: 28V

NF IECEx Dust Ignition-proof Approval

Certificate Number: See Certificate
Ex tD A22 IP66 T135 (-40°C < T

a

< 60°C)

Vmax = 28V

CONDITIONS OF INSTALLING N1 AND N7:
The Apparatus is not capable of withstanding the 500V insulation test required by
Clause 9.4 of EN 60079-15: 2005. This must be taken into account when installing the
apparatus.