Quick Installation Guide

00825-0100-4420, Rev CA
June 2007

1420 Wireless Gateway

9

S

TEP

3

CONTINUED

...

To configure the 1420 for a Serial connection:

Table 4: Serial Communication Settings on page 15 is available to assist in recording the
necessary information.

1. Configure 1420 Serial Communication Settings

a. Access the 1420 Web Interface with Administrator access
b. Navigate to Setup>Modbus>Communication
c. Click Enable Modbus

d. Configure the 1420 Modbus Communication settings to match the Host Modbus

settings

NOTE:
Modbus communications will fail if they are not configured identically on the Host
and the 1420.

e. Click Submit and proceed with restart

2. When configuration is completed, disconnect the PC/laptop from the 1420 and return the

PC/laptop to its previous network settings.