Installing C2RPS-CHAS8 into the Rack

SecureStack C2 Installation Guide 2-5

An ambient temperature of between 5°C (41°F) and 40°C (104°F) must be maintained 
at the installation site with fluctuations of less than 10°C (18°F) per hour.

Rack Mounting the Chassis

Refer to 

Figure 2‐2

 and proceed as follows to install the chassis into a 19‐inch rack:

1.

Position the chassis between the vertical frame members

and align the mounting 

holes in the chassis brackets with those in the rack frame. 

2.

Fasten the chassis securely to the frame using ten mounting screws (user‐supplied). 

Caution: To ensure proper ventilation and prevent overheating, leave a minimum
clearance space of 101.6 cm (4.0 in.) at the front and rear of the chassis.

Precaución: Para asegurar una buena ventilación y evitar que el sistema se
sobrecaliente, deje un espacio mínimo de 10.16 cm (4 pulgadas.) con respecto a la parte
delantera y trasera del chasis.

Warning: Before installing the chassis into a rack, ensure that the rack can support the
device(s) without compromising the stability of the rack. Otherwise, personal injury and/or
equipment damage may result.
Advertencia: Antes de instalar el chassis en un rack, asegurarse que el rack puede
soportar el(los) dispositivo(s) sin comprometer la estabilidad del mismo. De otra forma
puede suceder algun tipo de daño personal o del equipo.
Warnhinweis: Schützen Sie sich vor Verletzungen und Geräteschaden, überzeugen Sie
sich vor der Installation des Chassis in das Rack, von dessen Stabilität.