Piping Connections and Piping Access Points

16

Figure 15 Liebert XD system with prefabricated piping assembly and Liebert XD Flex Pipe

5.6

Disconnecting a Liebert XDCF With Liebert XD Flex Pipe From a Liebert XD
System

Tools Required

• Two adjustable wrenches, maximum adjustment size of 2-1/2 inches
• Phillips head #2 screwdriver

1. Close the service valve in the supply line to the Liebert XDCF (smaller coupler).
2. Close the service valve in the return line to the Liebert XDCF (larger coupler).
3. Locate and have at the ready the caps and plugs for both ends of the supply and return couplers.
4. Loosen the female supply coupler from the male supply coupler (smaller coupler). This requires

two adjustable wrenches. Refer to Figure 14.

5. The Liebert XDCF side of the female coupler must be held stationary while the collar on the

coupler is being loosened. Refer to Figure 14.

6. Disconnect the coupler.

NOTE
Before uninstalling a Liebert XDCF with Liebert XD Flex Pipe from the prefabricated piping

mains: Close the supply service valve, wait approximately two minutes, then close the return

service valve.
Read all instructions before beginning.

Return Service Valve
Make sure valve is
open after system
leak check

Supply Service Valve
Make sure valve is
open after system
leak check

Return Flex pipe

Supply Flex Pipe

Return
Main

Supply Main

Advertising