General product information

3

2.0

G

ENERAL

PRODUCT

INFORMATION

The Liebert XDCF

is a self-contained module designed to cool Egenera’s BladeFrame EX cabinets

and equipment without exhausting heat into the room.
Liebert XDCF modules consist of a sheet-metal frame, coil and filter dryer. It has no moving parts

and needs no electricity.
The Liebert XDCF system consists of:

• Liebert XDCF modules—upper and lower models are available
• Liebert XD Flex Pipe (optional)—connects Liebert XDCF units to supply and return piping (ships

with Liebert XDCF)

• Liebert XD Piping—delivers R-134a refrigerant through flexible piping
• Liebert XDP or Liebert XDC—supplies R-134a refrigerant to Liebert XDCF modules

(see Liebert XDP or Liebert XDC user manual for required chiller or drycooler)

Liebert XDCF modules attach to the rear of the Egenera BladeFrame EX

cabinet. Heated air from

the BladeFrame cabinet is exhausted through the Liebert XDCF, which absorbs the heat. The cooled

air passes into the room and the heat is carried away by the Liebert XDCF’s R-134a refrigerant.

2.1

References

This document must be used together with site-specific documentation and documentation for other

parts of the system.

2.2

Parts Included With Liebert XDCF

• Installation manual (this document)
• Liebert XDCF module
• Mounting kit parts with the following items:

2.3

Room Preparation

The room should be well insulated and must have a sealed vapor barrier. The vapor barrier in the

ceiling and walls can be a polyethylene film. Paint on concrete walls and floors should contain either

rubber or plastic.

Outside or fresh air should be kept to a minimum when temperature and humidity must be tightly

controlled. Outside air adds to the cooling, heating, dehumidifying and humidifying loads of the site.

Doors should be properly sealed to minimize leaks and should not contain ventilation grilles.

Lower Module

Upper Module

Part

Qty Part

Qty

Lower mounting bracket

1 Top unit mounting angle

1

Top deflector panel

(two-pieces)

1 Bottom deflector panel

(two-pieces)

1

Liebert XD Flex Pipe retainers

3 Liebert XD Flex Pipe retainers

3

10-32 screws

3 10-32 screws

2

10-32 nut

2 10-32 nut

1

Liebert XD Flex Pipe support panel

1

NOTE
The vapor barrier is the single most important requirement for maintaining environmental

control in the conditioned space.