Advanced Microprocessor with Graphics Control Setup

24

4.7.1 Setup Operation

The SETUP OPERATION menu permits the review and/or adjustment of the unit configuration. This

may include:

Cold Start Delay

This feature, also referred to as Positive Start or Winter Start Kit, allows for the low pressure switch

to be ignored for the programmed time during a cold start of the compressor. Entering a “0” for this

time will bypass this feature. A “1”, will bypass the low pressure switch for one minute, a “2” for two

minutes, etc. The programmed value can be from 0 to 3 minutes. This delay is factory set to 0 for

water cooled, glycol-cooled, and GLYCOOL

units. Typically, only air cooled units need a “Winter

Start” time.

Auto Restart Delay

This feature allows for the unit to restart automatically after a loss of power. The programmed value

is .1 minute (6 seconds) intervals. A programmed value of zero (0) would require the user to manually

press the ON/OFF switch to start the unit, i.e. no auto restart. The purpose of this feature is to pre-

vent several units from starting at the same time after a loss of power. The message “Restart delay --

Please wait” will be displayed when the system is in the AUTO RESTART mode. (It is suggested mul-

tiple unit installations be programmed with different auto restart times.)

IR Flush Overfill (infrared humidifiers only)

An autoflush system automatically controls a water makeup valve to maintain proper level in the

infrared humidifier water pan during humidifier operation. If humidification is needed and 15 hours

have elapsed since the last time the humidifier was on, then the humidifier is held off until the valve

completes an initial fill of the humidifier pan. This pre-fill is about 30 seconds. The valve continues to

fill and flush the pan for about 4 minutes.
During humidifier operation, with the flush rate set at the default of 150%, the valve is opened peri-

odically to add water to the pan (about 40 seconds every 9 and 1/2 minutes of humidifier operation).

This adds enough water to the pan to cause about a third of the total water used to be flushed out the

overflow standpipe located in the humidifier pan. This action helps to remove solids from the pan. The

flush rate is adjustable from 110% to 500%. If the water quality is poor, it may be desirable to

increase the water flushing action above the normal 150% rate. Also, if the supply water pressure is

low, the flush rate adjustment can be increased so that sufficient water level is maintained during

humidification.

Chilled Water/Hot Water/Econ-O-Coil Flush

This feature will flush the respective coil for three (3) minutes after the programmed number of hours of

nonuse. For example, if the flush time is programmed with 24 hours on a hot water reheat type system,

and heating is not required for a 24 hour period, the hot water valve will be opened for 3 minutes to

allow the coil to be flushed. The programmed value can be from 0 (no flush) to 99 (99 hours of nonuse).

Display in Degrees

The control can be set to display readings and setpoints in either degrees Fahrenheit (F) or Celsius (C).

Default Settings and Ranges

See Table 9 below for the list of setup functions, their factory default values and the allowable ranges

for which they can be programmed.
Table 9

Setup functions and factory default values

Function

Default

Range

Cold Start Time Delay*

3

0 to 3 min (0 = no delay)

Restart Time Delay

0.1

0 to 9.9 min (0 =manual restart)

Infrared Fill Rate

150

110 to 500%

Chilled/Hot Water

Coil Flush

24

0 to 99 hrs (also Econ-o-coil)

F/C Degrees

F

C or F

*Factory set to 0 for water-cooled, glycol, and GLYCOOL units.