Response by Control Type—Advanced Microprocessor Controls

41

5.4.2 Water Detection Display

The water detection display is designed to graphically display the location of water under a raised

floor when connected to an LT750 water detection system. The graphical floor plan screen shows a

30 x 16 grid. Each square represents one standard floor tile (approximately 2 ft. x 2ft.).

Figure 6

Connecting the LT750

Physical Connections

The example above shows the 4-20 mA output of LT750 connected to Analog Input #1 (41 and 42) on

the external inputs terminal strip. This strip is provided on units ordered with analog inputs. (If this

strip is not installed, there is a field installation kit available from your Liebert representative.)
The 4-20 mA output of the LT750 must be connected to the first analog input, as shown. TB4 is the

water detected relay output. It can be connected to any one of the four special alarm inputs. TB5 is

the cable fault relay output. It can also be connected to any one of the four special alarm inputs.

Setup

The following description assumes wiring connections as shown in Figure 6.
First, verify that special alarms 1 and 2 are Enabled to either Warning or Urgent type. Do this by

selecting View/Set Alarms from the Main Menu. Then, select Setup Alarms. Follow the instructions on

the display to select the required type for Custom Alarm #1 and Custom Alarm #2 if not already set.
Next, select the alarm message for Custom Alarm #1 and #2. From the Main Menu, select View/Set

Alarms. Then, select Setup Custom Alarms. Then, select Setup Custom Alarm Text. Define Custom

Alarm #1 to be Custom 1. (Custom 1 is the default message that will be displayed if a message has never

been programmed.) Next, select the text for custom alarm #2 to be Water Under Floor. Now, change the

message Custom 1 to LT750 Cable Fault. This is done by selecting the Change Custom Text 1 menu

item in the Setup Custom Alarms menu. Follow the instructions on the screen to change the message.
The slope and intercept values of Analog Input #1 are used to calculate the location of water. These

values should initially be set to zero. The default values are zero, but it may be a good idea to verify

those values. They can be viewed by selecting Analog/Digital Inputs from the Main Menu, then Setup

Analog Inputs.
See 4.4.6 - Setup Water Detect Floor Plan for more information.