OP-STOP DC INJECTION BRAKE

Page 8

3.3 ADJUSTMENTS

3.3.1 POTENTIOMETERS

POT

NAME

RANGE DEFAULT

SETTING

DESCRIPTION

RV1 BRAKING

TIME

1-60 sec

30%

Adjust the braking time
CW rotation increases the time

RV2

TORQUE

100-300%

50%

Adjust DC current
CW increases the braking torque
(current)

3.3.2 1LINK SELECTION

LINK

NAME

POSITION DESCRIPTION

JP1

VOLTAGE

LEVEL

LO
(Normal)

Braking action starts when motor starter has opened
and the motor terminal voltage has decreased to
30% of the line voltage.

HI

Braking action starts when motor starter has opened
and the motor terminal voltage has decreased to
80% of the line voltage. See important notes below.



HI setting is only used when the stopping time is critical and must be around 1-2 seconds. For this
application 300% DC current is not adequate. Consult factory before using this jumper position.

When the OP-STOP is set on the HI level a current surge could occur due to the motor CEMF and
the free wheeling action of the power circuit.

3.3.3 PUSHBUTTON

PUSHBUTTON

NAME

DESCRIPTION

SW1

RESET

Reset IOC fault trip