OP-STOP DC INJECTION BRAKE

Page 14

MODEL

MOTOR

AMPS

BURDEN

RESISTOR (¼ W)

EFFECTIVE CT

RATIO

SS6-15 with DCI

10.0

68

Ω

750 : 1

15.0

47

Ω

DCI-20

or

SS6-30 with DCI

20.0

39

Ω

750 : 1

30.0

27

Ω

DCI-40 or

SS6-50 with DCI

40.0

39

Ω

1500 : 1

50.0

33

Ω

DCI-80 or

SS6-80 with DCI

60.0

39

Ω

2500 : 1

80.0

33

Ω

DCI-125 or

SS6-125 with DCI

100.0

27

Ω

2500 : 1

125.0

22

Ω

DCI-200 or

SS6-200 with DCI

150.0

18

Ω

2500 : 1

200.0

12

Ω

DCI-300 or

SS6-360 with DCI

200.0

27Ω

5000 : 1

300.0

18

Ω

DCI-500 or

SS6-500 with DCI

400.0

22

Ω

8500 : 1

500.0

18

Ω

4.5.2 WITH POWER ON

4.5.2.1 Run the motor up to full speed and command the starter off. If the motor reaches zero

speed from the DC injection cycle, close the switch to the Disable Input to disable the
braking.

4.5.2.2 Re-adjust the braking torque pot, RV2, if the actual braking time has to be increased or

decreased to bring the motor to zero speed.

4.5.2.3 Once the braking torque is set, then adjust RV1 to match the DC injection time with the

actual stopping time of the motor. Typically, the injection should decease when the motor
is at zero speed or shortly after. LD1, DC INJCT is an indication of braking. Each 10%
graduation in RV1 corresponds to approximately 6 seconds.

WARNING!

ALLOW TIME FOR THE MOTOR TO COOL BEFORE ANOTHER

START / STOP SEQUENCE IS INITIATED

FREQUENT START / STOP COULD CAUSE MOTOR DAMAGE

DUE TO OVERHEATING