OP-STOP DC INJECTION BRAKE

Page 4

2 SPECIFICATIONS

2.1 POWER RATING

POWER

200-600VAC, 50/60 Hz

CONTROL

115 VAC, 50 Hz or 120 VAC, 60 Hz

RATING

Intermittent duty, See Section 2.2

300% for 30 seconds, once every 30 minutes

All models have 1600V PIV SCR's

CONTACTS

DC injection relay contacts rated at 1A, 120VAC

PROTECTION Short circuit by HRC fuses or circuit breaker

(supplied upon request)

Voltage surge protection by snubber's and MOV's across the SCR's

2.2 CURRENT AND FUSE RATING

CURRENT RATING

DCI

MODEL

AMPS MOTOR

HP @ 575 V

MOTOR

HP @ 460V

FUSE
AMPS

SCR

TYPE

DCI-20

20.0

20.0

15.0

20.0

Module

DCI-40

40.0

40.0

30.0

40.0

Module

DCI-80

80.0

75.0

60.0

80.0

Module

DCI-125

125.0

125.0

100.0

125.0

Module

DCI-200

200.0

200.0

150.0

200.0

Disc

DCI-300

300.0

300.0

250.0

300.0

Disc

DCI-500

500.0

500.0

400.0

500.0

Disc

2.2.1 NOTES

2.2.1.1 The HP listing is for reference only. For proper selection use the current rating.

2.2.1.2 The fuses recommended are Class J time-delay type. This fuse is being suggested even

though it may not protect the SCR in an output shorted condition while braking. It will
protect the unit when starting to operate into a shorted output. In the case of a shorted
SCR, the fuse is there to clear the fault only.

2.2.1.3 The RMS AC line current is equal to : AC RMS = DC Amps x

√ Duty Cycle Assuming

10A motor, OP-STOP set at 300% current (30 A DC), free wheeling for 70% of the
cycle, then the AC current is 16A.

2.2.1.4 All OP-STOP models are built without cooling fans because they are short duty rated.