Thermo Pride C Premiere Series User Manual

Page 13

Advertising
background image

INITIAL START UP OF OUTDO

er), attempts to operate the air conditioner and take gauged pressure readings

may be unsuccessful, as unusually low pressures will be observed on the suction line. This type of operation

OR CONDENSING UNIT

On cooler days (65

° F or low

may give the impression of an undercharged unit. Such is NOT necessarily the case. The low-pressure

ing so much

eat from the refrigerant. Sub-cooling occurs and results in very low pressures. Adding refrigerant in cold

h pressure limit during warm or

ot weather. Line pressures should not be taken for test purposes when the outdoor temperature is below 70

°

onditioner on a day of 45

° F or cooler.

temp. of 76– 78ºF is reached then

t must be between 8 –

is done by comparing the gauge temp.

n the suction line to the measured

temp. on the low side of the condenser. The

en increase charge.

e temperature of the liquid line leaving

ture.

ature will be about 10ºF lower than its gauge temperature.

the difference is less add charge. If the difference is greater remove charge. The system should run for

r condensing units are equipped with gauge ports to connect both liquid and

ction line pressure gauges. Refrigerant hoses must be the type which incorporate a "finger" to depress the

s

hort

rvice hoses are recommended to minimize refrigerant losses.

reading may exist because of the large condenser surface area and the cold ambient air remov
h
weather will result in an overcharged unit, which may then trip out on hig
h
F since a false reading may occur. Do not attempt to operate the air c


When an inside
superheat measuremen
10ºF. This
of R-410A o

difference is the superheat. If the superheat is less
that 8

ºF decrease charge. If the superheat

is more than 10ºF th

Another check on system charge, would be to
measure th
the condenser and it’s R-410A gauge tempera

For proper operation, the measured liquid temper
If
at least 10 minutes before rechecking.

All Thermo Pride outdoo
su
core. Connections may be made to ports at any time; even while unit is in operation. Follow EPA guideline
in connecting service equipment to refrigerant lines. For example: The use of quick connects and s
se

: Refrigerant is under pressure. Guard against refrigerant spraying into the face o

on skin. Always wear protective eq

r

uipment, i.e. safety glasses or goggles and gloves when working

with refrigerant.

: R-410a systems operate at higher pressures than R-22 systems. Do not use R-22

service equipment or components on R-410a equipment. Service equipment must be rated for R410a.

Line pressures on an operating air conditioning unit will vary with outdoor temperatures. As outdoor
temperatures rise, pressures will also rise. See pressure temperature chart for system line pressures at
different temperatures.

The suction pressure is the most significant when reading gauges. If a unit is suspected of low charge, unit
should be recharged using the suction pressure as a guide. Unit is fully charged when proper suction
pressure is obtained. Any additional refrigerant may cause damage or additional problems.

ABLE : APP

E OP RATIN

Insi

Temp

O

side T

T

1

ROXIMAT

E

G PRESSURES

de

. vs.

ut

emp. vs. Liquid

Suction Press.

Press.

INSIDE

TEMP.

SUCTION

PRESS.

OUTSIDE

TEMP.

LIQUID
PRESS

(ºF)

(P.S.I.G.)

(P.S.I.G.)

(ºF)

65 106

70 266

70 117

75 286

72 121

80 308

74 126

85 331

76 131

90 354

80 140

95 380

85 154

100 406

90 168

105 434

13

Advertising